Plan Review Notes
Plan Review Notes For Permit 14100350
Permit Number 14100350
Review Stop B
Sequence Number 1
Notes
Date Text
2014-11-06 09:45:29BUILDING PLAN REVIEW
 PERMIT: 14100350
 ADD: 10130 NORTHLAKE BLVD.
 CONT: HAWKINS
 TEL: (305-796-9695
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. NOV. 06/2014
 ACTION: DENIED
  
 1) SHEET D-1, A-1 & S-3 ALL SHOW A NEW WALK-UP/
 DRIVE-UP WINDOW. THE S-3 SHEET PROVIDES THE WIND DESIGN
 CRITERIA BUT NOT THE PRESSUES ASSOCIATED WITH THE NEW
 EXTERIOR WALL OPENING. THE A-11 SHEET SHOWS PRESSURES
 OF +36/ -39, BUT THERE IS NO WIND DESIGN CRITERIA FOR
 THE DESIN OF THESE PRESSUES, ARE THEY VULT OR VASD,
 WHAT EXPOSURE, HEIGHT ADJUSTMENT FACTORS????? PLEASE
 PROVIDE THE PRESSURES FOR THE NEW OPENING. COMPONENTS &
 CLADDING PRESSURES POSITVE & NEGATIVE TABLE 1609.2(2) .
  
 2) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(B) WINDOWS
  
 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) SHEET A11 DETAILS B2 & B4 BOTH INDICATE THE NEW
 PHARMACY WINDOW TO BE A FIXED WINDOW A YKK NOA
 05-0301.06. THIS MIAMI-DADE REPORT EXPIRED ON
 06/16/2010. THERE IS A DISCREPANCY BETWEEN THIS SHEET
 AND A-1. SHEET A-1 INDICATES THE NEW WINDOW IS TO BE A
 COMBINATION WINDOW/ COMMERCIAL DRAWER UNIT, E. F. BAVIS
 AUTOEYOR UNIT WITH AUDIO FOR THE HEARING IMPAIRED.
 DISCREPANCY IN PLANS, NOTE WITH THIS UNIT THE WINDOW
 ILL BE LOWER THAN DRAWN ON SHEET A11/ DETAIL B4. 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 5) THE PLANS DO NOT PROVIDE ANY DETAILS SHOWING THE
 CHECK OUT COUNTERS COMPLY WITH 2010 FL ACCESS. CODE
 904.3.
  
 6) SHEET A-6 SHOWS INTERIOR ELEVATIONS BUT AGAIN THE
 PLANS DO NOT SHOW COMPLIANCE WITH 2010 FL ACCESS. CODE
 904.3.3 & 904.3.4 CHECK WRITING SURFACES & SALES AND
 SERVICE COUNTERS.
  
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  