| 2014-11-06 09:45:29 | BUILDING PLAN REVIEW |
| | PERMIT: 14100350 |
| | ADD: 10130 NORTHLAKE BLVD. |
| | CONT: HAWKINS |
| | TEL: (305-796-9695 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. NOV. 06/2014 |
| | ACTION: DENIED |
| | |
| | 1) SHEET D-1, A-1 & S-3 ALL SHOW A NEW WALK-UP/ |
| | DRIVE-UP WINDOW. THE S-3 SHEET PROVIDES THE WIND DESIGN |
| | CRITERIA BUT NOT THE PRESSUES ASSOCIATED WITH THE NEW |
| | EXTERIOR WALL OPENING. THE A-11 SHEET SHOWS PRESSURES |
| | OF +36/ -39, BUT THERE IS NO WIND DESIGN CRITERIA FOR |
| | THE DESIN OF THESE PRESSUES, ARE THEY VULT OR VASD, |
| | WHAT EXPOSURE, HEIGHT ADJUSTMENT FACTORS????? PLEASE |
| | PROVIDE THE PRESSURES FOR THE NEW OPENING. COMPONENTS & |
| | CLADDING PRESSURES POSITVE & NEGATIVE TABLE 1609.2(2) . |
| | |
| | 2) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(B) WINDOWS |
| | |
| | 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 4) SHEET A11 DETAILS B2 & B4 BOTH INDICATE THE NEW |
| | PHARMACY WINDOW TO BE A FIXED WINDOW A YKK NOA |
| | 05-0301.06. THIS MIAMI-DADE REPORT EXPIRED ON |
| | 06/16/2010. THERE IS A DISCREPANCY BETWEEN THIS SHEET |
| | AND A-1. SHEET A-1 INDICATES THE NEW WINDOW IS TO BE A |
| | COMBINATION WINDOW/ COMMERCIAL DRAWER UNIT, E. F. BAVIS |
| | AUTOEYOR UNIT WITH AUDIO FOR THE HEARING IMPAIRED. |
| | DISCREPANCY IN PLANS, NOTE WITH THIS UNIT THE WINDOW |
| | ILL BE LOWER THAN DRAWN ON SHEET A11/ DETAIL B4. 2010 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 5) THE PLANS DO NOT PROVIDE ANY DETAILS SHOWING THE |
| | CHECK OUT COUNTERS COMPLY WITH 2010 FL ACCESS. CODE |
| | 904.3. |
| | |
| | 6) SHEET A-6 SHOWS INTERIOR ELEVATIONS BUT AGAIN THE |
| | PLANS DO NOT SHOW COMPLIANCE WITH 2010 FL ACCESS. CODE |
| | 904.3.3 & 904.3.4 CHECK WRITING SURFACES & SALES AND |
| | SERVICE COUNTERS. |
| | |
| | |
| | TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO |
| | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA |
| | TUS.ASPX FOR PERMIT STATUS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |