Plan Review Notes
Plan Review Notes For Permit 14100349
Permit Number 14100349
Review Stop E
Sequence Number 1
Notes
Date Text
2014-10-24 08:24:0710/24/2014
 PROJECT: AUTOZONE
 PERMIT#: 14100349
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE WIND LOAD CALCULATIONS IN ACCORDANCE WITH
 THE FBC CHAPTERS 26 THROUGH 30 OF ASCE 7 OR THE
 PROVISIONS OF THE ALTERNATE ALL HEIGHTS METHOD IN THE
 FBC SECTION 1609.6.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  