| 2014-10-09 18:59:30 | PLAN REVIEW COMMENTS | | | | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | BUILDING | | | | | | 1) THE DESIGN PRESSURE OF -60 PSF FOR THE CERTAINTEED | | | MODIFIED ROOFING SYSTEM SPECIFIED ON PAGE 15 OF NOA | | | NO.14-0224.03 IS TOO LOW FOR ROOF ZONES 2 AND 3 IN | | | EXPOSURE C WITH A 170 MPH VULT WIND SPEED. SUBMIT TWO | | | SETS OF RAS 117 CALCULATIONS FOR ENHANCED FASTENING OF | | | THE PERIMETER AND CORNER AREAS AS REQUIRED BY | | | LIMITATION #7 ON PAGE 16 OF THE NOA. NOTE: CERTAINTEED | | | HAS A PRODUCT APPROVAL FOR A MODIFIED ROOFING SYSTEM | | | (FL 16709) THAT HAS THE ENHANCED FASTENING REQUIREMENTS | | | INCLUDED. | | | | | | 2) FBC - R905.2.2 SLOPE. | | | ASPHALT SHINGLES SHALL ONLY BE USED ON ROOF SLOPES OF | | | TWO UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) OR | | | GREATER. FOR ROOF SLOPES FROM TWO UNITS VERTICAL IN 12 | | | UNITS HORIZONTAL (2:12) UP TO FOUR UNITS VERTICAL IN 12 | | | UNITS HORIZONTAL (4:12), TWO LAYERS OF UNDERLAYMENT | | | COMPLYING WITH ASTM D 226, TYPE I OR TYPE II, ASTM D | | | 4869, TYPE I OR TYPE II OR ASTM D 6757 IS REQUIRED IN | | | ACCORDANCE WITH SECTION R905.2.7. |
|