| Plan Review Notes For Permit 14100317 |
| Permit Number |
14100317 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-10-09 15:54:57 | PLAN REVIEW COMMENTS | | | | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | BUILDING | | | | | | 1) THE CONTRACT INDICATES THAT THE ROOF TILE WILL BE | | | MECHANICALLY FASTENED. SPECIFY THE TYPE AND NUMBER OF | | | FASTENERS THAT WILL BE USED TO INSTALL THE ROOF TILE. | | | SUBMIT 2 COPIES OF THE PAGES WITH THE APPLICABLE TABLES | | | FOR THE REQUIRED OVERTURN MOMENT FOR A 6/12 ROOF SLOPE | | | IN EXPOSURE C AND THE MECHANICAL FASTENING ATTACHMENT | | | RESISTANCE VALUES. FBC 107.2.1 | | | | | | 2) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | REQUIRED BY DCA RULE 9N-3 FOR THE 3M AH160 FOAM | | | ADHESIVE. |
|