| Date |
Text |
| 2014-12-11 08:58:43 | PLAN REVIEW COMMENTS |
| | |
| | |
| | 2ND REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | BUILDING |
| | |
| | 1) FBC 107.2.1 ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. |
| | |
| | 2) 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| | SHALL BE DRAWN TO A MINIMUM 1/8 INCH |
| | SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE |
| | MEDIUM. THE BUILDING OFFICIAL MAY |
| | ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS |
| | FOR PLANS AND SPECIFICATIONS, IN |
| | ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION |
| | PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| | OTHER ITEMS RELATED TO RECORDS |
| | MANAGEMENT. SPECIFY THE SCALE OF THE DRAWINGS ON THE |
| | PLANS. |
| | |
| | 3) 602.2 TYPES I AND II. |
| | TYPES I AND II CONSTRUCTION ARE THOSE TYPES OF |
| | CONSTRUCTION IN WHICH THE BUILDING ELEMENTS LISTED IN |
| | TABLE 601 ARE OF NONCOMBUSTIBLE MATERIALS, EXCEPT AS |
| | PERMITTED IN SECTION 603 AND ELSEWHERE IN THIS CODE. |
| | SPECIFY THE MATERIALS USED TO CONSTRUCT THE SOFFIT, |
| | WHICH SHALL COMPLY WITH THIS SECTION. |
| | |
| | 4) 2) FBC 107.2.1 PROVIDE FRAMING DETAILS FOR THE NEW |
| | SOFFITS. SPECIFY THE FRAMING MATERIALS, THE SPACING AND |
| | THE NUMBER AND TYPE OF FASTENERS THAT WILL BE USED. |
| | |
| | 5) FBC 803 SPECIFY THE INTERIOR FINISHING MATERIAL AND |
| | THE THICKNESS OF THE MATERIAL THAT WILL BE USED TO |
| | COVER THE SOFFIT. (I.E. DRYWALL, WOOD PANELS, ETC.) |
| | |
| | |
| | |