Date Text
2014-11-08 11:44:0411/8/2014
 PROJECT: OFFICE RENNOVATION
 PERMIT#: 14100274
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) REVISE THE RISER DIAGRAM SO THAT THERE IS A MAIN
 OCPD AFTER THE METER, NOT BEFORE, AND INDICATE HOW THE
 FEEDER TO PANEL 4H IS PROTECTED.
  
 2) REVISE THE RISER DIAGRAM TO INDICATE HOW THE FEEDER
 FROM THE TRANSFORMER SECONDARY FEEDING PANEL 4L IS
 PROTECTED.
  
 3) REVISE THE RISER DIAGRAM TO INDICATE WHAT IS FEEDING
 PANEL 4L-1. IT IS INDICATED AS A 150AMP PANEL. THE
 RISER SHOWS EXISTING 4,#3 AND A #6 GROUND FROM PANEL 4L
 BUT NO BREAKER IN THE PANEL SCHEDULE 4L. REVISE PANEL
 SCHEDULE AND LOAD CALCULATION ACCORDINGLY.
  
 4) EMERGENCY LIGHTS WERE ADDED TO THE SHEET E-1.
 INDICATE WHICH ARE EXISTING OR NEW. THEY SHOULD BE
 PLACED TO ILLUMINATE THE PATH OF TRAVEL FOR THE MEANS
 OF EGRESS. A LIFE SAFETY PLAN HAS NOT BEEN INCLUDED.
 PLEASE PROVIDE A LIFE SAFETY PLAN WITH EMERGENCY AND
 EXIT LIGHTING INSTALLED TO ILLUMINATE THE MEANS OF
 EGRESS. NFPA 101 SECTION 7.10.1.5.1, NEC 700.12,
 700.16,
  
 5) INDICATE THE CIRCUIT THAT THE EXIT AND EMERGENCY
 LIGHHTING WILL BE CONNECTED TO. NEC 700.12(F)
  
 6) INDICATE AND PROVIDE THE LOCATION FOR THE ELECTRICAL
 SERVICE AND PANELS. VERIFY AND PROVIDE THE REQUIRED
 CLEARANCES AS PER THE NEC 110.26
  
 7) VERIFY THAT THE NEW PROPSED WORK STATIONS WILL NOT
 BOCK ACCESS TO THE EXISTING OR NEW OUTLETS OR JUNCTION
 BOXES. 110.26
  
 8) PROVIDE A NOTE ON PLANS REGARDING THE LIMITATIONS OF
 USE FOR MULTI-WIRE BRANCH CIRCUITS. NEC 210.4, 605.8(D)
  
 9) PROVIDE THE MEANS TO DISCONNECT SIMULTANEOUSLY ALL
 UNGROUNDED CONDUCTORS AT THE PANELBOARD WHERE THE
 BRANCH CIRCUIT ORIGINATES. NEC 605.7
  
 10) PROVIDE A NOTE ON PLANS REGARDING THE VOLTAGE
 LIMITATIONS AND SEPARATION WITH BARRIERS REQUIRED FOR
 SWITCHES AND ADJACENT DEVICES. NEC 404.8
  
 11) PROVIDE A LIGHHTING PLAN AND INDICATE EXISTING AND
 NEW PLUS INDICATE HOW THE LIGHTING AND SWITCHING OF
 LIGHTING IS AFFECTED BY THE RENOVATION.
  
 12) INDICATE HOW THE LIGHTING COMPLIES WITH THE
 FBC-ENERGY SECTION 505.2 LIGHTING CONTROLS ARE
 MANDATORY IN BUILDINGS 5000SQUARE FEET OR LARGER. FBC-E
 505.2
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  