| 2014-11-08 11:44:04 | 11/8/2014 |
| | PROJECT: OFFICE RENNOVATION |
| | PERMIT#: 14100274 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) REVISE THE RISER DIAGRAM SO THAT THERE IS A MAIN |
| | OCPD AFTER THE METER, NOT BEFORE, AND INDICATE HOW THE |
| | FEEDER TO PANEL 4H IS PROTECTED. |
| | |
| | 2) REVISE THE RISER DIAGRAM TO INDICATE HOW THE FEEDER |
| | FROM THE TRANSFORMER SECONDARY FEEDING PANEL 4L IS |
| | PROTECTED. |
| | |
| | 3) REVISE THE RISER DIAGRAM TO INDICATE WHAT IS FEEDING |
| | PANEL 4L-1. IT IS INDICATED AS A 150AMP PANEL. THE |
| | RISER SHOWS EXISTING 4,#3 AND A #6 GROUND FROM PANEL 4L |
| | BUT NO BREAKER IN THE PANEL SCHEDULE 4L. REVISE PANEL |
| | SCHEDULE AND LOAD CALCULATION ACCORDINGLY. |
| | |
| | 4) EMERGENCY LIGHTS WERE ADDED TO THE SHEET E-1. |
| | INDICATE WHICH ARE EXISTING OR NEW. THEY SHOULD BE |
| | PLACED TO ILLUMINATE THE PATH OF TRAVEL FOR THE MEANS |
| | OF EGRESS. A LIFE SAFETY PLAN HAS NOT BEEN INCLUDED. |
| | PLEASE PROVIDE A LIFE SAFETY PLAN WITH EMERGENCY AND |
| | EXIT LIGHTING INSTALLED TO ILLUMINATE THE MEANS OF |
| | EGRESS. NFPA 101 SECTION 7.10.1.5.1, NEC 700.12, |
| | 700.16, |
| | |
| | 5) INDICATE THE CIRCUIT THAT THE EXIT AND EMERGENCY |
| | LIGHHTING WILL BE CONNECTED TO. NEC 700.12(F) |
| | |
| | 6) INDICATE AND PROVIDE THE LOCATION FOR THE ELECTRICAL |
| | SERVICE AND PANELS. VERIFY AND PROVIDE THE REQUIRED |
| | CLEARANCES AS PER THE NEC 110.26 |
| | |
| | 7) VERIFY THAT THE NEW PROPSED WORK STATIONS WILL NOT |
| | BOCK ACCESS TO THE EXISTING OR NEW OUTLETS OR JUNCTION |
| | BOXES. 110.26 |
| | |
| | 8) PROVIDE A NOTE ON PLANS REGARDING THE LIMITATIONS OF |
| | USE FOR MULTI-WIRE BRANCH CIRCUITS. NEC 210.4, 605.8(D) |
| | |
| | 9) PROVIDE THE MEANS TO DISCONNECT SIMULTANEOUSLY ALL |
| | UNGROUNDED CONDUCTORS AT THE PANELBOARD WHERE THE |
| | BRANCH CIRCUIT ORIGINATES. NEC 605.7 |
| | |
| | 10) PROVIDE A NOTE ON PLANS REGARDING THE VOLTAGE |
| | LIMITATIONS AND SEPARATION WITH BARRIERS REQUIRED FOR |
| | SWITCHES AND ADJACENT DEVICES. NEC 404.8 |
| | |
| | 11) PROVIDE A LIGHHTING PLAN AND INDICATE EXISTING AND |
| | NEW PLUS INDICATE HOW THE LIGHTING AND SWITCHING OF |
| | LIGHTING IS AFFECTED BY THE RENOVATION. |
| | |
| | 12) INDICATE HOW THE LIGHTING COMPLIES WITH THE |
| | FBC-ENERGY SECTION 505.2 LIGHTING CONTROLS ARE |
| | MANDATORY IN BUILDINGS 5000SQUARE FEET OR LARGER. FBC-E |
| | 505.2 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |