| Plan Review Notes For Permit 14100274 |
| Permit Number |
14100274 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-10-10 13:59:35 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | THE EXTENT OF THE REMODEL OR REVISION IS UNCLEAR AND | | | DOES NOT INDICATE SUFFICIENT DETAIL TO ADDRESS LIFE | | | SAFETY CONCERNS OF THE PROPOSED PROJECT. | | | | | | A DEAD-END COORIDOR IS BEING PROPOSED; HOWEVER, THE | | | PROPOSED FLOOR PLAN DOES NOT INDICATE ANY DIMENSIONS. | | | | | | TWO ROOMS ARE SHOWING; HOWEVER, THERE IS NO DOORS | | | INDICATED. | | | | | | A LIFE SAFETY PLAN IS NOT INCLUDED AND SHALL BE | | | INCLUDING THE RE-SUBMITTAL. THE CCUPANY LOAD, EXIT | | | PATHS, EXITS, EXIT SIGNS AND EMERGENCY LIGHTING SHALL | | | BE INCLUDED. | | | | | | THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE | | | FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND | | | COMPLIANCE. | | | | | | THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | | CONSTRUCTION PERIOD. | | | | | | ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER | | | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND | | | BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | | | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, | | | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE | | | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL | | | AND COMPLETE PROTECTION IS RETURNED. | | | |
|