| 2014-10-14 13:17:38 | 14100274 | | | 1615 FORUM PL. #4D | | | INTERIOR ALTERATIONS | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS | | | | | | CONSTRUCTION DRAWINGS DO NOT HAVE SUFFICIENT CLARITY. | | | INDICATE WHICH ELECTRICAL CIRCUITS ARE NEW AND WHICH | | | ARE EXISTING. WPB/FBC 107.3.5 | | | | | | ON THE ELECTRIC PLAN SHOW THE LOCATION OF TRANSFORMER | | | AND PANELS. SHOW ALL REQUIRED ACCESS AND SAFE WORKING | | | CLEARANCES FOR THE PANEL BOARDS. NEC 110.26 | | | | | | PROVIDE A FIRE STOP DETAIL FOR ANY WALL OR FLOOR | | | PENETRATIONS OF FIRE RATED ASSEMBLIES. NEC 300.21 | | | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | | FOR THE PANEL BOARDS AND DISCONNECTING MEANS. NEC | | | 110.22, 110.16, 110.22 | | | | | | PROVIDE A NOTE ON PLANS REGARDING THE LIMITATIONS OF | | | USE FOR MULTI-WIRE BRANCH CIRCUITS. NEC 210.4, 605.8(D) | | | | | | PROVIDE A NOTE ON PLANS REGARDING THE VOLTAGE | | | LIMITATIONS AND SEPARATION WITH BARRIERS REQUIRED FOR | | | SWITCHES AND ADJACENT DEVICES. NEC 404.8 | | | | | | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE | | | ALARM SYSTEMS, SECURITY AND DATA SYSTEMS. | | | | | | | | | ROBERT LECKY, CBO | | | ELECTRICAL PLANS REVIEW | | | 561-373-3701 | | | [email protected] | | | | | | |
|