 1615 FORUM PL. #4D
 INTERIOR ALTERATIONS
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS
  
 CONSTRUCTION DRAWINGS DO NOT HAVE SUFFICIENT CLARITY.
 INDICATE WHICH ELECTRICAL CIRCUITS ARE NEW AND WHICH
 ARE EXISTING. WPB/FBC 107.3.5
  
 ON THE ELECTRIC PLAN SHOW THE LOCATION OF TRANSFORMER
 AND PANELS. SHOW ALL REQUIRED ACCESS AND SAFE WORKING
 CLEARANCES FOR THE PANEL BOARDS. NEC 110.26
  
 PROVIDE A FIRE STOP DETAIL FOR ANY WALL OR FLOOR
 PENETRATIONS OF FIRE RATED ASSEMBLIES. NEC 300.21
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE PANEL BOARDS AND DISCONNECTING MEANS. NEC
 110.22, 110.16, 110.22
  
 PROVIDE A NOTE ON PLANS REGARDING THE LIMITATIONS OF
 USE FOR MULTI-WIRE BRANCH CIRCUITS. NEC 210.4, 605.8(D)
  
 PROVIDE A NOTE ON PLANS REGARDING THE VOLTAGE
 LIMITATIONS AND SEPARATION WITH BARRIERS REQUIRED FOR
 SWITCHES AND ADJACENT DEVICES. NEC 404.8
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE
 ALARM SYSTEMS, SECURITY AND DATA SYSTEMS.
  
  