| 2014-10-11 10:52:47 | BUILDING PLAN REVIEW |
| | PERMIT: 14100274 |
| | ADD: 1615 FORUM PLACE/ 4TH FLOOR |
| | CONT: CONSTRUCTION SUPERVISORS CORP. |
| | TEL: (561)667-2175 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. OCT. 11/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.2.1 |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS, |
| | 107.3.5.1.1 COMMERCIAL BUILDINGS: |
| | OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| | SHALL BE DETERMINED. |
| | MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE |
| | TABLE 503). NOTE THIS IS A HIGH RISE CONTSTRUCTION |
| | FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL INCLUDE |
| | THE FOLLOWING COMPONENTS: TENANT SEPARATION WALLS |
| | FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: |
| | EARLY WARNING SMOKE EVACUATION SYSTEMS |
| | SCHEMATIC FIRE SPRINKLERS / PRE-ENGINEERED SYSTEMS |
| | LIFE SAFETY PLAN TO INCLUDE: |
| | OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD |
| | GROSS |
| | NET |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| | ACCESSIBLE ROUTE |
| | TOILET AND BATHING FACILITIES |
| | DRINKING FOUNTAINS |
| | |
| | 2) THE EXISTING FLOOR PLAN VS THE PROPOSED FLOOR PLAN |
| | THE BOTTOM LEFT IT APPEARS WALLS ARE BEING REMOVED IN |
| | ANOTHER TENANT SPACE. THE BOTTOM LEFT EXISTING SHOWS A |
| | DOORWAY TO THE COMMON AREA, THE PROPOSED PLAN WHICH |
| | REMOVES 2 SMALL WALLS DOES NOT HAVE A ENTRY DOOR. |
| | PROVIDE A EXISTING BUILDING PLAN AND A NEW PROPOSED |
| | PLAN. THE SUBMITTED PLANS ARE CONFUSING TO WHERE THE |
| | WORK AREA IS LOCATED. |
| | |
| | 3) ON THE PERMIT APPLICATION AS WELL AS PLANS IDENTIFY |
| | THE TENANT SUITE NUMBER WHERE WORK IS TO BE PREFORMED. |
| | THE APPLICATION INDICATES THE FOURTH FLOOR. IS THIS A |
| | NEW TENNANT SUITE BEING CARVED OUT OF ANOTHER SUITE? |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION,107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTSCONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED.F] 501.2 ADDRESS |
| | IDENTIFICATION. |
| | |
| | 4) 1018.4 DEAD ENDS. |
| | WHERE MORE THAN ONE EXIT OR EXIT ACCESS DOORWAY IS |
| | REQUIRED, THE EXIT ACCESS SHALL BE ARRANGED SUCH THAT |
| | THERE ARE NO DEAD ENDS IN CORRIDORS MORE THAN 20 FEET |
| | (6096 MM) IN LENGTH. |
| | EXCEPTIONS: |
| | 1. IN OCCUPANCIES IN GROUP I-3 OF OCCUPANCY CONDITION |
| | 2, 3 OR 4 (SEE SECTION 308.4), THE DEAD END IN A |
| | CORRIDOR SHALL NOT EXCEED 50 FEET . |
| | 2. IN OCCUPANCIES IN GROUPS B, E, F, I-1, M, R-1, R-2, |
| | R-4, S AND U, WHERE THE BUILDING IS EQUIPPED THROUGHOUT |
| | WITH AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| | SECTION 903.3.1.1, THE LENGTH OF THE DEAD-END CORRIDORS |
| | SHALL NOT EXCEED 50 FEET (15 240 MM). |
| | 3. A DEAD-END CORRIDOR SHALL NOT BE LIMITED IN LENGTH |
| | WHERE THE LENGTH OF THE DEAD-END CORRIDOR IS LESS THAN |
| | 2.5 TIMES THE LEAST WIDTH OF THE DEAD-END CORRIDOR. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |