Plan Review Notes
Plan Review Notes For Permit 14100265
Permit Number 14100265
Review Stop B
Sequence Number 4
Notes
Date Text
2015-07-14 12:26:37****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 FBC FLORIDA BUILDING CODE 2010
  
 TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED
  
 FROM PREVIOUS LIST:
  
 1 - 3. OK (WHISPERMAT CS TEST REPORTS SUBMITTED).
  
 4. PROVIDE INFORMATION REGARDING THE EXISTING FLOOR
 COVERING TYPE AND WEIGHT AND THE PROPOSED FLOOR
 COVERING WEIGHT. ENGINEERING MAY BE REQUIRED TO
 DEMONSTRATE THAT THE EXISTING STRUCTURAL FLOOR SLAB CAN
 ACCOMODATE ADDITIONAL DEAD LOAD, IF APPLICABLE, FBC
 1604.1.
  
 2ND REVIEW - INSTALLATION PROPOSED IS OVER TWICE
 EXISTING WEIGHT. ESTIMATED WEIGHT IS UNCLEAR. WEIGHT
 INCLUDES 30 BAGS OF THINSET; WHAT SIZE BAGS? WHAT
 THICKNESS OF MORTAR BED IS PROPOSED? MARBLE/TRAVERTINE
 SIZE (24X24) AND WEIGHT PROVIDED, BUT NOT THICKNESS.
  
 UNLESS CONTRACTOR CAN DEMONSTRATE THAT PROPOSED WEIGHT
 IS WITHIN BUILDING DESIGN LIMITS, ENGINEERING WILL BE
 REQUIRED TO DETERMINE THAT EXISTING FLOOR CAN
 ACCOMODATE THE ADDITIONAL DEAD LOAD PROPOSED. A COPY OF
 THE ORIGINAL BUILDING PLANS MAY BE AVAILABLE. PLEASE
 CONTACT [email protected] AND [email protected] IF YOU WISH
 TO SUBMIT A PUBLIC RECORDS RESEARCH REQUEST.
  
 3RD REVIEW, NOT ADDRESSED. PER CONTRACTOR, THE EXISTING
 WEIGHT IS 2500 #, PROPOSED IS 6500 #. NO ENGINEERING OR
 OTHER INFORMATION PROVIDED TO DOCUMENT THE ABILITY OF
 THE EXISTING SLAB TO RESIST THE ADDITIONAL DEAD LOAD.
  
  