| Plan Review Notes For Permit 14100265 |
| Permit Number |
14100265 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2015-03-25 07:27:27 | ****CORRECTIONS**** | | | CONTRACTOR SUBMITTED FLAME SPREAD TEST ONLY PER MY | | | REQUEST | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 | | | [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2010 | | | | | | COMMENTS FROM PREVIOUS LIST APPLY. THE FLAME SPREAD | | | TEST PROVIDED DOES NOT INCLUDE THE PRODUCT PROPOSED | | | (PROFLEX 70SSC). | | | | | | THE TEST REPORT PROVIDED IS FOR PROFLEX MSC 90, RCU | | | 250, LV 100. AS DISCUSSED, THIS PRODUCT DOES NOT MEET | | | THE FLAME SPREAD OR SOUND SUPPRESSION REQUIREMENTS (SEE | | | PREVIOUS LIST). THIS PRODUCT IS TO BE REMOVED | | | IMMEDIATELY. | | | | | | |
|