| Date |
Text |
| 2014-10-23 08:47:59 | ****CORRECTIONS**** |
| | SPOKE WITH CONTRACTOR AND EXPLAINED COMMENTS IN LOBBY - |
| | TOLD HIM TO RESUBMIT SO HE COULD HAVE THE COMMENTS IN |
| | WRITING TO SEND TO MANUFACTURER |
| | GAVE HIM THE LIST OF PRODUCTS FOR WHICH WE HAVE 3 |
| | COMPLIANT TEST REPORTS BUT THE PRODUCT PROFLEX SSC HAS |
| | ALREADY BEEN INSTALLED |
| | ADVISED TO CONTACT MANUFACTURER WITH COMMENT LIST TO |
| | RESOLVE |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 |
| | [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2010 |
| | |
| | TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST, |
| | PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED |
| | THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE |
| | GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL |
| | NOT BE ALTERED. |
| | |
| | PLEASE PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | 2ND REVIEW - TEST REPORT PROVIDED HAS A SUSPENDED |
| | CEILING. AS THIS PRODUCT HAS ALREADY BEEN INSTALLED, |
| | PROVIDE A TEST REPORT WITHOUT A SUSPENDED CEILING OR |
| | SUBMIT UNDER ALTERNATIVE MATERIALS AND METHODS, CITY OF |
| | WEST PALM BEACH AMENDMENTS TO THE FBC, SECTION 104.11 |
| | (SEE BELOW FOR CODE LANGUAGE). |
| | |
| | 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART |
| | OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN |
| | DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW |
| | IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT |
| | BELOW WILL NOT BE ALTERED. |
| | |
| | PLEASE PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | 2ND REVIEW - TEST REPORT PROVIDED HAS A SUSPENDED |
| | CEILING; SEE COMMENT #1. |
| | |
| | 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM |
| | E 84 OR UL 723. |
| | |
| | 2ND REVIEW - TEST REPORT NOT SUBMITTED. SEE COMMENT #1. |
| | |
| | 4. PROVIDE INFORMATION REGARDING THE EXISTING FLOOR |
| | COVERING TYPE AND WEIGHT AND THE PROPOSED FLOOR |
| | COVERING WEIGHT. ENGINEERING MAY BE REQUIRED TO |
| | DEMONSTRATE THAT THE EXISTING STRUCTURAL FLOOR SLAB CAN |
| | ACCOMODATE ADDITIONAL DEAD LOAD, IF APPLICABLE, FBC |
| | 1604.1. |
| | |
| | 2ND REVIEW - INSTALLATION PROPOSED IS OVER TWICE |
| | EXISTING WEIGHT. ESTIMATED WEIGHT IS UNCLEAR. WEIGHT |
| | INCLUDES 30 BAGS OF THINSET; WHAT SIZE BAGS? WHAT |
| | THICKNESS OF MORTAR BED IS PROPOSED? MARBLE/TRAVERTINE |
| | SIZE (24X24) AND WEIGHT PROVIDED, BUT NOT THICKNESS. |
| | |
| | UNLESS CONTRACTOR CAN DEMONSTRATE THAT PROPOSED WEIGHT |
| | IS WITHIN BUILDING DESIGN LIMITS, ENGINEERING WILL BE |
| | REQUIRED TO DETERMINE THAT EXISTING FLOOR CAN |
| | ACCOMODATE THE ADDITIONAL DEAD LOAD PROPOSED. A COPY OF |
| | THE ORIGINAL BUILDING PLANS MAY BE AVAILABLE. PLEASE |
| | CONTACT [email protected] AND [email protected] IF YOU WISH |
| | TO SUBMIT A PUBLIC RECORDS RESEARCH REQUEST. |
| | |
| | |