| Notes |
| Date |
Text |
| 2014-10-08 15:50:06 | 700 SOUTH ROSEMARY AVENUE | | | PERMIT #14100254 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE PLANS INDICATE FIRE LANE WIDTHS BETWEEN 12-15 FEET | | | TO ALLOW ACCESS FOR EMERGENCY VEHICLES; HOWEVER, | | | PREVIOUS FIRE INSPECTIONS OF THESE EVENTS REVEALED | | | ADEQUATE CLEARANCES HAVE NOT BEEN MAINTAINED AT STREET | | | INTERSECTIONS, CROSSWALKS AND OTHER AREAS WHERE THE | | | STREET WIDTH IS REDUCED. ALSO SEVERAL CANOPIES HAD SUN | | | SHADE EXTENSIONS PROTRUDING INTO THE FIRE LANE | | | CLEARANCE AREA. PROVIDE UNOBSTRUCTED VERTICAL CLEARANCE | | | OF NOT LESS THAN 13 FEET 6 INCHES. | | | | | | FIRE HYDRANTS SHALL BE PROVIDED WITH CLEARANCES OF | | | 7'-6" TO THE FRONT AND SIDES AND 4'-0" TO THE BACKSIDE | | | OF THE STEAMER CAP. | | | | | | TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM | | | BUILDING STRUCTURES. | | | | | | POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS | | | LOCATIONS. | | | | | | GENERATORS AND OTHER INTERNAL COMBUSTION POWER SOURCES | | | SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 FEET | | | AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR | | | ENCLOSURE. | | | | | | EXTENSION CORDS AND OTHER POSSIBLE OBSTRUCTIONS IN THE | | | MEANS OF EGRESS SHALL BE PROPERLY SECURED OR COVERED TO | | | PREVENT A TRIPPING HAZARD. | | | | | | EGRESS PATHS SHALL BE MAINTAINED WITH VERTICAL | | | CLEARANCES OF 7'-6". | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|