2014-10-08 15:50:06700 SOUTH ROSEMARY AVENUE
 PERMIT #14100254
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PLANS INDICATE FIRE LANE WIDTHS BETWEEN 12-15 FEET
 TO ALLOW ACCESS FOR EMERGENCY VEHICLES; HOWEVER,
 PREVIOUS FIRE INSPECTIONS OF THESE EVENTS REVEALED
 ADEQUATE CLEARANCES HAVE NOT BEEN MAINTAINED AT STREET
 INTERSECTIONS, CROSSWALKS AND OTHER AREAS WHERE THE
 STREET WIDTH IS REDUCED. ALSO SEVERAL CANOPIES HAD SUN
 SHADE EXTENSIONS PROTRUDING INTO THE FIRE LANE
 CLEARANCE AREA. PROVIDE UNOBSTRUCTED VERTICAL CLEARANCE
 OF NOT LESS THAN 13 FEET 6 INCHES.
  
 FIRE HYDRANTS SHALL BE PROVIDED WITH CLEARANCES OF
 7'-6" TO THE FRONT AND SIDES AND 4'-0" TO THE BACKSIDE
 OF THE STEAMER CAP.
  
 TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM
 BUILDING STRUCTURES.
  
 POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 GENERATORS AND OTHER INTERNAL COMBUSTION POWER SOURCES
 SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 FEET
 AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR
 ENCLOSURE.
  
 EXTENSION CORDS AND OTHER POSSIBLE OBSTRUCTIONS IN THE
 MEANS OF EGRESS SHALL BE PROPERLY SECURED OR COVERED TO
 PREVENT A TRIPPING HAZARD.
  
 EGRESS PATHS SHALL BE MAINTAINED WITH VERTICAL
 CLEARANCES OF 7'-6".
  