| Plan Review Notes For Permit 14100228 |
| Permit Number |
14100228 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-10-09 12:03:42 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- INSTALLATION SCHEDULE SUBMITTED INDICATES THAT | | | SHUTTERS GLASS SEPARATION IS NOT APPLICABLE (NA). | | | PRODUCT APPROVAL FL11964-R1 SUBMITTED REQUIRES GLASS | | | SEPARATION. REVISE INSTALLATION SCHEDULE AS REQUIRED. | | | SEC. 107.2.1 CITY AMENDMENTS TO FBC. | | | | | | 2- INSTALLATION SCHEDULE SUBMITTED INDICATES THAT THE | | | BUILDING IS LOCATED IN EXPOSURE "D". THE DESIGN | | | PRESSURES SUBMITTED DON'T CORRESPOND TO A BUILDING WITH | | | A 20'-0" MEAN ROOF HEIGHT IN EXPOSURE "D". TABLE | | | R301.2(3) OF 2010 FBC-RESIDENTIAL. REVISE CALCULATIONS | | | OR PROVIDE 2 COPIES OF SIGNED AND SEALED CALCULATIONS. | | | SEC. 107.2.1.3 OF CITY AMENDMENTS TO FBC. | | | ***NOTE: CONNECTION TYPE "ALT. 14". AFTER DESIGN | | | PRESSURES ARE REVISED, VERIFY THAT PROPOSED CONNECTION | | | TYPE MEETS THE MAX. DESIGN PRESSURES AND MAX. PANEL | | | SPAN FOR ALL OPENINGS. FOR EXAMPLE: CHECK OPENING #9. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|