| Plan Review Notes For Permit 14100217 |
| Permit Number |
14100217 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-10-10 10:31:37 | CONDENSATE DISPOSAL IS NOT ALLOWED INTO THE SANITARY | | | SYSTEM, PROVIDE DISPOSAL IN REGARDS TO 307.2.1 BELOW | | | | | | FBC-M 307.2.1 CONDENSATE DISPOSAL. | | | CONDENSATE FROM ALL COOLING COILS AND EVAPORATORS SHALL | | | BE CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED | | | PLACE OF DISPOSAL. SUCH PIPING SHALL MAINTAIN A MINIMUM | | | HORIZONTAL SLOPE IN THE DIRECTION OF DISCHARGE OF NOT | | | LESS THAN ONE-EIGHTH UNIT VERTICAL IN 12 UNITS | | | HORIZONTAL (1-PERCENT SLOPE). CONDENSATE SHALL NOT | | | DISCHARGE INTO A STREET, ALLEY OR OTHER AREAS SO AS TO | | | CAUSE A NUISANCE. |
|