| 2014-12-18 11:15:47 | BUILDING PLAN REVIEW |
| | PERMIT: 14100194 |
| | ADD: 3416 S. DIXIE HWY |
| | CONT: JACOB ERECTING |
| | TEL: (561)741-1818 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: THURS. DEC. 18/2014 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE PROVIDE A SITE PLAN WITH THE PROPOSED |
| | LOCATION OF THE BUILDING ON THE LOT AND THE DISTANCE |
| | FROM PROPERTY LINES. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION,107.3.5 MINIMUM PLAN |
| | REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | 1. SITE PLAN & REQUIREMENTS: |
| | PARKING : CITY MUNI CODE REQUIRES A DOUBLE STRIPE |
| | 94-485. |
| | ACCESSIBLE EXITS |
| | THE LARGER OF THE 2 TENANTCIES REQUIRES 2 EXITS BECAUSE |
| | THE OCCUPANT LOAD IS OVER 50 OCCUPANTS (74 OCCUPANTS). |
| | THIS REQUIRES 2 EXITS FBC-B TABLE 1015.1. THE 2010 FBC- |
| | ACCESSIBILITY CODE 207.1 REFERS TO THE 2003 IBC-B 1007. |
| | 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS |
| | IS REQUIRED BY SECTION 1014.1 OR 1018.1 FROM ANY |
| | ACCESSIBLE SPACE, EACH ACCESIBLE PORTION OF THE SPACE |
| | SHALL BE SERVED BY NOT LESS THAN TWO ACCESSIBLE MEANS |
| | OF EGRESS. THE BACK EXIT DOES NOT SHOW AN ACCESIBLE |
| | EXIT DISCHARGE, YOU WOULD HAVE TO TRAVEL WITH A |
| | WHEELCHAIR BEHIND PARKED CARS THERE IS NO ACCESSIBLE |
| | WALKWAY TO TRAVEL ON TO GETTO THE PUBLIC WAY. |
| | |
| | 2) COMPLIED. SOILS REPORT. |
| | |
| | 3) COMPLIED. ENERGY CALCULATIONS WERE PROVIDED. |
| | |
| | 4 2ND REQUEST WIND PRESSURES FOR COMPONENTS AND |
| | CLADDING. SHEET S1 LIST THE WIND DESIGN CRITERIA, WITH |
| | A C EXPOSURE. THE COMMENT RESPONSE INDICATED THE WINDOW |
| | & DOOR PRESSURES COULD NOW BE FOUND ON THE ELEVATION |
| | SHEET A-3.0. |
| | |
| | 4A) THE PRESURES REPRESENTED ON THIS SHEET APPEAR TO BE |
| | TAKEN AS A B EXPOSURE AT 15 FT. |
| | |
| | 4B) THE COMMENT RESPONSE ALSO INDICATED THE ROOFING |
| | PRESSURES ARE TO BE FOUND ON SHEET S2.1. THESE |
| | PRESSURES ALSO APPEAR TO BE LOW AS TAKEN AS A B |
| | EXPOSURE AT 15 FT. PLEASE ALSO NOTE THE PARAPET IS LESS |
| | THAN 3 FEET IN HEIGHT WHICH WILL MEAN THERE IS A ROOF |
| | CORNER ZONE AND HIGHER ASSOCIATED PRESSURES. THE |
| | ELEVATIONS SHOWN ON A-3.0 OF THE BAR JOIST, IS THE |
| | JOIST BEARING POINT. THE VERTICAL HEIGHT OF THE BAR |
| | JOIST, B-DECK, AND 6 INCHES OF INSULATION (ENERGY |
| | CALCS.) PUTS THE APPROX. MEAN FINISH ROOF HEIGHT AT |
| | 18FT. 10 INCHES TO 18 FT. 11 IN., THE TOP OF PARAPET IS |
| | AT 21 FT. 4 IN. OR LESS THAN 3 FT OF PARAPET. |
| | |
| | |
| | 5) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING.FLORIDA DEPARTMENT OF |
| | COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(D) ROOFING PRODUCTS AND ASSEMBLIES NO SUB-SYSTEM |
| | HAS BEEN IDENTIFIED, ENHANCED FASTENING WILL BE |
| | REQUIRED FOR THE ROOF INSULATION AS WELL AS THE ROOFING |
| | SYSTEM, SEE IF LIMITATION #7 OR #9. |
| | (G) PRE-ENGINEERED A/C STANDS/ ROOF TOP CURBS |
| | |
| | 5A) WITH ROOF TOP A/C CONDENSORS THE M6.1 INDICATES THE |
| | USE OF ROOF TOP CURBS, THERE IS NO FRAMING DETAILS FOR |
| | THE ANCHORING OF THE ROOF TOP CURBS, NOR DOES THE PLANS |
| | PROVIDE THE AMOUNT OF FASTENERS, AND SIZE OF FASTENERS |
| | IT WILL TAKE TO ANCHOR THE CURB TO THE ROOF FRAMING. |
| | THE PLANS ALSO WILL NEED TO PROVIDE DETAILS OF THE |
| | ANCHORING THE ROOF TOP UNITS TO THE ROOF CURB. |
| | |
| | 6) ROOFING APPROVAL ONCE THE SUB-SYSTEM IS |
| | IDENTIFIED.2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 7-10) COMPLIED. |
| | |
| | 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO |
| | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA |
| | TUS.ASPX FOR PERMIT STATUS. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |