| 2015-01-20 12:02:39 | BUILDING PLAN REVIEW |
| | PERMIT: 14100194 |
| | ADD: 3416 S. DIXIE HWY |
| | CONT: JACOB ERECTING |
| | TEL: (561)741-1818 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: MON. JAN 20/2015 |
| | ACTION: BUILDING PROVISO |
| | |
| | 1) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING.FLORIDA DEPARTMENT OF |
| | COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(D) ROOFING PRODUCTS AND ASSEMBLIES NO SUB-SYSTEM |
| | HAS BEEN IDENTIFIED, ENHANCED FASTENING WILL BE |
| | REQUIRED FOR THE ROOF INSULATION AS WELL AS THE ROOFING |
| | SYSTEM, SEE IF LIMITATION #7 OR #9. |
| | |
| | ONCE THE CONTRACTOR PICKS WHICH ROOFING SUB-SYSTEM IS |
| | TO BE APPLIED TO THE ROOF DECK, THE PRODUCT APPROVAL |
| | MUST BE REVIEWED BY THE DESIGNER OF RECORD AND SHOP |
| | DRAWING STAMP OF APPROVAL APPLIED. RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |