Plan Review Notes
Plan Review Notes For Permit 14100194
Permit Number 14100194
Review Stop P
Sequence Number 1
Notes
Date Text
2014-10-28 14:48:29WPB AMEND. TO 2010 FBC SEC.107.2.1.
 1) SHOW THE SQUARE FOOTAGE FOR EACH TENANT SPACE ON THE
 PLAN AND THE OCCUPANT LOAD FOR EACH SPACE.
 2) ROOM #102 - THE SINK SHALL COMPLY WITH THE 2010 FL.
 ACCESSIBILITY CODE SECS. 212, & 606. A 30 INCH BY 48
 INCH CLEAR FLOOR SPACE COMPLYING WITH SEC. 305 SHALL BE
 POSITIONED FOR A FORWARD APPROACH, AND KNEE AND TOE
 CLEARANCES COMPLYING WITH SEC.306 SHALL BE PROVIDED.
 3) SHT. A-3.1 - SHOW THE DIMENSIONS OF THE CLEAR FLOOR
 SPACE FOR THE FIXTURES ON THE PLAN.COMPLY W/ FL.
 ACCESSIBILITY CODE SECS.305.3, 604.3.1,.
 4) THE TOILET ROOMS SHALL HAVE A TURNING SPACE
 COMPLYING WITH FL. ACCESS. CODE SECS.304, 304.3.1,
 304.3.2. ( EITHER A 60 INCH MINIMUM DIAMETER CIRCULAR
 SPACE OR A T-SHAPED SPACE WITHIN A 60 INCH SQUARE
 MINIMUM WITH ARMS AND BASE 36 INCHES WIDE MINIMUM.)
 5) SHT. A-2.1 - DETAIL #4 - DETAIL SHOWS THE HEIGHT OF
 THE SCUPPER AS 5 INCES YET IT ALSO STATES SCUPPER TO BE
 4 INCHES IN HEIGHT.CLARIFY.
 6) SHT.A-2.1 - DETAIL #7 REFERS TO DETAIL # 5/A-2.0 -
 THERE IS NO SUCH DETAIL ON A-2.0. CLARIFY.
 7) SHT. A-2.0 - ROOF DRAINAGE CALS CALLS OUT PRIMARY &
 SECONDARY SCUPPERS AS 4" X 8" YET DETAIL #4 ON SHT.
 A-2.1 SHOWS 4" X 12" SCUPPERS. DETAIL #6 ON SHT. A-2.1.
 SHOWS THE TYPICAL SCUPPER AS 4" X 12". CLARIFY.
 8) DRINKING FOUNTAINS MAY BE REQD. IN THE TENANT SPACES
 DEPENDING UPON THE OCCUPANT LOAD PER THE FL. PLUMBING
 CODE TABLE 403.1.
 9) SEPARATE SANITARY FACILITIES MAY BE REQD. FOR MALES
 AND FEMALES PER TABLE 403.1. THIS IS BASE ON SQUARE
 FOOTAGE OF THE FACILITY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  