Plan Review Notes
Plan Review Notes For Permit 14100194
Permit Number 14100194
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-10-14 15:08:213416 SOUTH DIXIE HIGHWAY
 PERMIT #14100194
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: PROVIDE A SITE PLAN.
  
 SHEET LS-1.0: REMOVE CODE REFERENCES TO THE 2006
 EDITION; UPDATE THE CODE LIST TO REFERENCE THE 2010
 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
  
 SHEET A-1.0: DOOR #101 SERVES MORE THAN 50 PERSONS AND
 WILL BE REQUIRED TO SWING IN THE DIRECTION OF EGRESS.
  
 SHEET A-1.0 TENANT SEPARATION WALL: PER SECTION
 8.3.2.4, EACH FIRE BARRIER SHALL BE PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING READING FIRE
 BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT
 LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER. PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY
 SHALL BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE.
  
 SHEET A-1.0 MAIN ENTRANCE DOOR: KEYED LOCKS OR
 THUMB-TURN LOCK TO BE EQUIPPED WITH AN ?OPEN/LOCKED?
 INDICATOR WINDOW (SUCH AS ADAMS RITE 4089 OR SIMILAR).
  
 SHEET A-3.0: PER SECTION 10.12.1.2 (NFPA 1), PROVIDE
 BUILDING ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL
 BE ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES
 IN HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  