| 2014-10-22 11:33:47 | 10/22/2014 |
| | PROJECT: 3416 S DIXIE HWY |
| | PERMIT#: 14100194 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET E-1.1 |
| | A) SITE LIGHTING. WIND LOADS ON EVERY BUILDING OR |
| | STRUCTURE SHALL BE DETERMINED IN ACCORDANCE WITH |
| | CHAPTERS 26 THROUGH 30 OF ASCE 7 OR THE PROVISIONS OF |
| | THE ALTERNATE ALL HEIGHTS METHOD IN SECTION 1609.6. |
| | WIND SHALL BE ASSUMED TO COME FROM ANY HORIZONTAL |
| | DIRECTION AND WIND PRESSURES SHALL BE ASSUMED TO ACT |
| | NORMAL TO THE SURFACE CONSIDERED. PROVIDE WIND LOAD |
| | CALCULATIONS INCLUDING MANUFACTURER SPECIFICATIONS AND |
| | SUBMITTALS ON POLES AND LUMINAIRES. |
| | B) 505.2.4 EXTERIOR LIGHTING CONTROLS. |
| | LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN |
| | SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF |
| | TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT |
| | IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED |
| | DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR |
| | DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A |
| | COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN |
| | ASTRONOMICAL TIME SWITCH. |
| | |
| | 2) SHEET E3.1 |
| | OUTLETS INDICATED IN THE FIRE RATED TENANT SEPARATION |
| | WALL SHALL BE SEPARATED BY A MINIMUM ORF 24" OR |
| | PROTECTED BY A FIRE RATED MATERIAL APPROVED FOR THAT |
| | USE. FBC 713.3.1.2. |
| | |
| | 3) ONE 125VOLT, SINGLE-PHASE, 15 OR 20AMP GFI |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HEATING, |
| | AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND |
| | WITHIN 25FT OF THE HEATING, AIR-CONDITIONING, AND |
| | REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET SHALL |
| | NOT BE CONNECTED TO THE LOAD SIDE OF THE EQUIPMENT |
| | DISCONNECTING MEANS. NEC 210.63 SEE 210.8(A)(3), VERIFY |
| | THE REQUIRED OUTLETS ARE EXISTING OR INDICATE NEW |
| | OUTLETS INCLUDING THE CIRCUIT IN THE CORRESPONDING |
| | PANELBOARD. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |