Plan Review Notes
Plan Review Notes For Permit 14100194
Permit Number 14100194
Review Stop E
Sequence Number 1
Notes
Date Text
2014-10-22 11:33:4710/22/2014
 PROJECT: 3416 S DIXIE HWY
 PERMIT#: 14100194
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) SHEET E-1.1
 A) SITE LIGHTING. WIND LOADS ON EVERY BUILDING OR
 STRUCTURE SHALL BE DETERMINED IN ACCORDANCE WITH
 CHAPTERS 26 THROUGH 30 OF ASCE 7 OR THE PROVISIONS OF
 THE ALTERNATE ALL HEIGHTS METHOD IN SECTION 1609.6.
 WIND SHALL BE ASSUMED TO COME FROM ANY HORIZONTAL
 DIRECTION AND WIND PRESSURES SHALL BE ASSUMED TO ACT
 NORMAL TO THE SURFACE CONSIDERED. PROVIDE WIND LOAD
 CALCULATIONS INCLUDING MANUFACTURER SPECIFICATIONS AND
 SUBMITTALS ON POLES AND LUMINAIRES.
 B) 505.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN
 SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF
 TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT
 IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED
 DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A
 COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN
 ASTRONOMICAL TIME SWITCH.
  
 2) SHEET E3.1
 OUTLETS INDICATED IN THE FIRE RATED TENANT SEPARATION
 WALL SHALL BE SEPARATED BY A MINIMUM ORF 24" OR
 PROTECTED BY A FIRE RATED MATERIAL APPROVED FOR THAT
 USE. FBC 713.3.1.2.
  
 3) ONE 125VOLT, SINGLE-PHASE, 15 OR 20AMP GFI
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND
 WITHIN 25FT OF THE HEATING, AIR-CONDITIONING, AND
 REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET SHALL
 NOT BE CONNECTED TO THE LOAD SIDE OF THE EQUIPMENT
 DISCONNECTING MEANS. NEC 210.63 SEE 210.8(A)(3), VERIFY
 THE REQUIRED OUTLETS ARE EXISTING OR INDICATE NEW
 OUTLETS INCLUDING THE CIRCUIT IN THE CORRESPONDING
 PANELBOARD.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  