| 2014-10-08 09:40:20 | WPB AMEND. TO 2010 FBC SEC.107.2.1. | | | 1) SUBMIT A SITE PLAN/SURVEY THAT SHOWS THE LOCATRION | | | OF THE FOUNTAIN EQUIPMENT. | | | 2) A BACKFLOW PREVENTER IS REQUIRED ON THE FILL LINE. | | | INDICATE THE TYPE, MAKE, MODEL & LOCATION OF THE | | | DEVICE. SUBMIT MANUF. SPECS. ON THE DEVICE. | | | 3) SHT. 1-NOTE #1 REFERENCES THE 2010 FLORIDA BUILDING | | | CODE RESIDENTIAL. THE SCOPE OF THIS WORK FALLS UNDER | | | THE 2010 FLORIDA BUILDING CODE, BUILDING. REVISE THE | | | NOTE. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|