| Date |
Text |
| 2014-10-08 10:23:34 | 10/8/2014 |
| | PROJECT: MORSE LIFE FOUNTAIN |
| | PERMIT#: 14100168 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE SITE PLAN TO INDICATE THE LOCATIONS OF THE |
| | ELECTRICAL SUPPLY EQUIPMENT AND THE EQUIPMENT TO |
| | RECIEVE ELECTRICAL SUPPLY AND TO INDICATE ANY EXISTING |
| | OR PROPOSED EQUIPMENT, OUTLETS OR LIGHTING WITHIN THE |
| | VECINITY OF THE FOUNTAIN. WPB AMENDMENTS TO FBC |
| | 107.3.2, NEC 680 |
| | |
| | 2) PROVIDE AN ELECTRICAL DETAIL PLAN TO INDICATE THE |
| | ELECTRICAL CIRCUITRY FROM THE SOURCE TO THE EQUIPMENT |
| | TO BE CONNECTED. WPB AMENDMENTS TO FBC 107.3.2, NEC 680 |
| | |
| | 3) PROVIDE A GROUNDING DETAIL TO INDICATE THE |
| | EQUIPOTENTIAL GROUND PATH. NEC 680.26 |
| | |
| | 4) PROVIDE MANUFACTURER DATA SHEETS ON ALL EQUIPMENT |
| | AND LIGHTS ASSOCIATED WITH THE FOUNTAIN. NEC 110.3(B) |
| | AND 680 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |