| Plan Review Notes For Permit 14100113 |
| Permit Number |
14100113 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-10-27 10:06:56 | TO TL'S DESK | | | | | | | | 2014-10-27 09:59:36 | 10/27/2014 | | | PROJECT: INMAN RESIDENCE | | | PERMIT#: 14100113 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 2ND ELECTRICAL PLAN REVIEW | | | ACTION: PASS WITH EXCEPTION | | | | | | 1) VERIFY THE REQUIRED MASTER BATHROOM CIRCUIT AND | | | OUTLET LOCATIONS AND INDICATE WHETHER EXISTING OR NEW. | | | AT LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED | | | TO SUPPLY BATHROOM RECEPTACLE OUTLET(S) NEC210.11(C)(3) | | | | | | 2) VERIFY THE ELECTRICAL SYSTEM VOLTAGE. THE PLAN | | | INDICATES THE PANEL IS 120/208V 3 PHASE 4 WIRE BUT THE | | | LOAD CALCULATION INDICATES A 120/208V 1 PHASE | | | CALCULATION. WPB AMENDMENTS TO THE FBC. | | | | | | 3) FBC 2704 BONDING METAL FRAMING MEMBERS: | | | METAL FRAMING MEMBERS SHALL BE BONDED TO THE EQUIPMENT | | | GROUNDING CONDUCTOR FOR THE CIRCUIT THAT MAY ENERGIZE | | | THE FRAMING AND BE SIZED IN ACCORDANCE WITH THE NEC | | | TABLE 250.122. FOR THE PURPOSE OF THIS SECTION, A | | | GROUNDED METAL OUTLET BOX ATTACHED TO THE FRAMING SHALL | | | BE PERMITTED. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|