| | BUILDING PLAN REVIEW |
| | PERMIT: 14100113 |
| | ADD: 701 S. OLIVE AVE. # 1519 |
| | CONT: THE COTTAGE CO. |
| | TEL: (772)766-5800 |
| | |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MON. OCT. 27/ 2014 |
| | |
| | ACTION: BUILDING PROVISO |
| | BUILDING APPROVED WITH EXCEPTION! |
| | |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 1) PRODUCT SPECS FOR PROTECTO WHISPER MAT CS WERE |
| | SUBMITTED AS PART OF THE 2ND REVIEW. THIS PRODUCT DOES |
| | NOT PROVIDE TESTING MEETING THE SOUND REQUIREMENTS OR |
| | FLAME SPREAD & SMOKE DEVELOPMENT: |
| | |
| | 1A) 2010 FBC-B 1207.3 STRUCTURE BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492--04. |
| | NO PRODUCT TESTING REPORTS WERE SUBMITTED, ONLY THE |
| | MANUFACTURERS SALES BROCHURE STATING IT MEETS THESE |
| | REQUIREMENTS. |
| | |
| | 1B) THE SUBMITTED SALES BROCHURE STATES THIS PRODUCT IS |
| | CONSTRUCTED OF A CROSSED LINK POLY-OLEFIN FOAM SHEET |
| | COMBINED WITH AGGRESSIVE RUBBERIZED ADHESIVE & A |
| | POLYESTER MESH FABRIC. MUST MEET THESE FIRE AND SMOKE |
| | DEVELOPMENT TEST. |
| | THE 2010 FBC-B SECTION 603.1.1(3) |
| | 2. THERMAL AND ACOUSTICAL INSULATION, OTHER THAN FOAM |
| | PLASTICS, HAVING A FLAME SPREAD INDEX OF NOT MORE THAN |
| | 25. |
| | 3. FOAM PLASTICS IN ACCORDANCE WITH CHAPTER 26. |
| | |
| | 2603.3 SURFACE-BURNING CHARACTERISTICS. |
| | UNLESS OTHERWISE INDICATED IN THIS SECTION, FOAM |
| | PLASTIC INSULATION AND FOAM PLASTIC CORES OF |
| | MANUFACTURED ASSEMBLIES SHALL HAVE A FLAME SPREAD INDEX |
| | OF NOT MORE THAN 75 AND A SMOKE-DEVELOPED INDEX OF NOT |
| | MORE THAN 450 WHERE TESTED IN THE MAXIMUM THICKNESS |
| | INTENDED FOR USE IN ACCORDANCE WITH ASTM E 84 OR UL |
| | 723. LOOSE FILL-TYPE FOAM PLASTIC INSULATION SHALL BE |
| | TESTED AS BOARD STOCK FOR THE FLAME SPREAD AND |
| | SMOKE-DEVELOPED INDEXES. |
| | |