| 2014-10-07 10:05:23 | 10/7/2014 |
| | PROJECT: INMAN RESIDENCE |
| | PERMIT#: 14100113 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | ELECTRICAL PLAN REVIEW |
| | ACTION: |
| | |
| | 1) PROVIDE RISER DIAGRAM AND LOAD CALCULATION |
| | INDICATING THE CAPACITY OF THE ELECTRICAL SERVICE AND |
| | PANEL TO SUPPORT THE ADDITIONAL LOAD. . |
| | |
| | 2) INDICATE THE LOCATION OF THE ELECTRICAL SERVICE. WPB |
| | AMENDMENTS 107.3.2 |
| | |
| | 3) SHEET A2 DETAIL 5 "ELEVATION DEN" INDICATES AN 80" |
| | TV. IS THERE AN OUTLET REQUIRED THERE TO POWER THE TV? |
| | IS THERE A COAXIAL, CAT5(6) OR HDMI CABLE TO FEED THE |
| | SATALITE/CABLE/AV SIGNAL TO THE TV? IF SO FROM WHERE? |
| | |
| | 4) NEC 210.11 (C) DWELLING UNITS. |
| | (1) SMALL-APPLIANCE BRANCH CIRCUITS. IN ADDITION TO THE |
| | NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF |
| | THIS SECTION, TWO OR MORE 20-AMPERE SMALL-APPLIANCE |
| | BRANCH CIRCUITS SHALL BE PROVIDED FOR ALL RECEPTACLE |
| | OUTLETS SPECIFIED BY 210.52(B). |
| | (2) LAUNDRY BRANCH CIRCUITS. IN ADDITION TO THE NUMBER |
| | OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF THIS |
| | SECTION, AT LEAST ONE ADDITIONAL 20-AMPERE BRANCH |
| | CIRCUIT SHALL BE PROVIDED TO SUPPLY THE LAUNDRY |
| | RECEPTACLE OUTLET(S) REQUIRED BY 210.52(F). THIS |
| | CIRCUIT SHALL HAVE NO OTHER OUTLETS. |
| | (3) BATHROOM BRANCH CIRCUITS. IN ADDITION TO THE NUMBER |
| | OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF THIS |
| | SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE |
| | PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH |
| | CIRCUITS SHALL HAVE NO OTHER OUTLETS. |
| | PROVIDE AND INDICATE THE REQUIRED OUTLETS ON THE PLANS. |
| | |
| | 5) 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION |
| | FOR PERSONNEL. (A) DWELLING UNITS. ALL 125-VOLT, |
| | SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES INSTALLED |
| | IN THE LOCATIONS SPECIFIED IN |
| | (1) THROUGH (8) SHALL HAVE GROUND-FAULT |
| | CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. (1) |
| | BATHROOMS. PROVIDE AND INDICATE THE REQUIRED OUTLETS ON |
| | THE PLANS. |
| | |
| | 6) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| | RESISTANT AND AFCI PROTECTED. NEC 210.1, 406.11 REVISE |
| | PLANS ACCORDINGLY. |
| | |
| | 7) INDICATE SWITCHING FOR WALL SCONCES, RECESSED |
| | LIGHTS, AND JUNCTION BOXES. |
| | |
| | 8) PROVIDE MANUFACTURER PRODUCT DATA SHEETS ON MASTER |
| | BATH FIXTURE. INDICATE ELEVATION OVER TUB FOR |
| | INSTALLATION OF FIXTURE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |