 PROJECT: INMAN RESIDENCE
 PERMIT#: 14100113
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 ELECTRICAL PLAN REVIEW
 ACTION:
  
 1) PROVIDE RISER DIAGRAM AND LOAD CALCULATION
 INDICATING THE CAPACITY OF THE ELECTRICAL SERVICE AND
 PANEL TO SUPPORT THE ADDITIONAL LOAD. .
  
 2) INDICATE THE LOCATION OF THE ELECTRICAL SERVICE. WPB
 AMENDMENTS 107.3.2
  
 3) SHEET A2 DETAIL 5 "ELEVATION DEN" INDICATES AN 80"
 TV. IS THERE AN OUTLET REQUIRED THERE TO POWER THE TV?
 IS THERE A COAXIAL, CAT5(6) OR HDMI CABLE TO FEED THE
 SATALITE/CABLE/AV SIGNAL TO THE TV? IF SO FROM WHERE?
  
 4) NEC 210.11 (C) DWELLING UNITS.
 (1) SMALL-APPLIANCE BRANCH CIRCUITS. IN ADDITION TO THE
 NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF
 THIS SECTION, TWO OR MORE 20-AMPERE SMALL-APPLIANCE
 BRANCH CIRCUITS SHALL BE PROVIDED FOR ALL RECEPTACLE
 OUTLETS SPECIFIED BY 210.52(B).
 (2) LAUNDRY BRANCH CIRCUITS. IN ADDITION TO THE NUMBER
 OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF THIS
 SECTION, AT LEAST ONE ADDITIONAL 20-AMPERE BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY THE LAUNDRY
 RECEPTACLE OUTLET(S) REQUIRED BY 210.52(F). THIS
 CIRCUIT SHALL HAVE NO OTHER OUTLETS.
 (3) BATHROOM BRANCH CIRCUITS. IN ADDITION TO THE NUMBER
 OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF THIS
 SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS.
 PROVIDE AND INDICATE THE REQUIRED OUTLETS ON THE PLANS.
  
 5) 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION
 FOR PERSONNEL. (A) DWELLING UNITS. ALL 125-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES INSTALLED
 IN THE LOCATIONS SPECIFIED IN
 (1) THROUGH (8) SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. (1)
 BATHROOMS. PROVIDE AND INDICATE THE REQUIRED OUTLETS ON
 THE PLANS.
  
 6) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.1, 406.11 REVISE
 PLANS ACCORDINGLY.
  
 7) INDICATE SWITCHING FOR WALL SCONCES, RECESSED
 LIGHTS, AND JUNCTION BOXES.
  
 8) PROVIDE MANUFACTURER PRODUCT DATA SHEETS ON MASTER
 BATH FIXTURE. INDICATE ELEVATION OVER TUB FOR
 INSTALLATION OF FIXTURE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  