| 2014-10-11 13:02:08 | BUILDING PLAN REVIEW |
| | PERMIT: 14100113 |
| | ADD: 701 S. OLIVE AVE. # 1519 |
| | CONT: THE COTTAGE CO. |
| | TEL: (772)766-5800 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. OCT. 11/ 2014 |
| | ACTION: BUILDING PROVISO |
| | |
| | 1) SHEET D1 NOTE INDICATES NO WORK TO BE COMPLETED TO |
| | FLOOR FINISH. THERE ARE WALLS THAT ARE BEING REMOVED, |
| | IF ONLY REPAIRING OF FLOOR THEN NO FLOOR INSULATION IS |
| | REQUIRED. IF THE WHOLE BATHROOM FLOOR IS BEING REMOVED |
| | AND A NEW FLOOR INSTALLED, THEN DOCUMENTS FOR THE |
| | FOLLOWING CODE SECTIONS ARE REQUIRED: |
| | 2010 FBC-B 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | 805.1.3 INSULATING BOARDS. |
| | COMBUSTIBLE INSULATING BOARDS NOT MORE THAN 1/2 INCH |
| | (12.7 MM) THICK AND COVERED WITH FINISH FLOORING ARE |
| | PERMITTED WHERE ATTACHED DIRECTLY TO A NONCOMBUSTIBLE |
| | FLOOR ASSEMBLY . |
| | |