2014-10-11 13:02:08BUILDING PLAN REVIEW
 PERMIT: 14100113
 ADD: 701 S. OLIVE AVE. # 1519
 CONT: THE COTTAGE CO.
 TEL: (772)766-5800
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. OCT. 11/ 2014
 ACTION: BUILDING PROVISO
  
 1) SHEET D1 NOTE INDICATES NO WORK TO BE COMPLETED TO
 FLOOR FINISH. THERE ARE WALLS THAT ARE BEING REMOVED,
 IF ONLY REPAIRING OF FLOOR THEN NO FLOOR INSULATION IS
 REQUIRED. IF THE WHOLE BATHROOM FLOOR IS BEING REMOVED
 AND A NEW FLOOR INSTALLED, THEN DOCUMENTS FOR THE
 FOLLOWING CODE SECTIONS ARE REQUIRED:
 2010 FBC-B 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
 805.1.3 INSULATING BOARDS.
 COMBUSTIBLE INSULATING BOARDS NOT MORE THAN 1/2 INCH
 (12.7 MM) THICK AND COVERED WITH FINISH FLOORING ARE
 PERMITTED WHERE ATTACHED DIRECTLY TO A NONCOMBUSTIBLE
 FLOOR ASSEMBLY .
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER