| 2015-02-09 09:56:21 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | COMMENTS FROM PREVIOUS LIST, NOT ADDRESSED: |
| | |
| | 1. SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE |
| | WITH THE ANCHOR CHARTS ON SHEET 11 (FOR EXAMPLE, 1 TOP, |
| | 2 BOTTOM, ETC.). FOR TAPCONS, MASONRY SUBSTRATE, NOT |
| | ALL CONNECTION TYPES ARE ALLOWED AND ALL REQUIRE ANCHOR |
| | SPACING OF 4 1/2" OR 5". 12" IS PROPOSED. |
| | |
| | 2. SUBSTRATE STATED IS "CONC. BLK". MOST CBS STRUCTURES |
| | HAVE A CONCRETE TOP SUBSTRATE, MASONRY BOTTOM |
| | SUBSTRATE. |
| | |
| | NEW COMMENT: |
| | |
| | 3. THE APPLICATION STATES THAT SCOPE IS TO INSTALL 2 |
| | WINDOWS AND 2 DOORS, BUT THE PLAN DOES NOT INDICATE |
| | WHICH WINDOWS ARE INCLUDED IN THE SCOPE. FBC 107, |
| | REVISE PLAN TO INDICATE WHICH WINDOWS ARE INCLUDED IN |
| | THE SCOPE OF THIS PERMIT OR REVISE APPLICATION. |
| | |
| | 4. VALUE IS TOO LOW, FBC 109. VALUE SHOULD INCLUDE THE |
| | VALUE OF LABOR, MATERIALS, OVERHEAD, PROFIT, |
| | ENGINEERING/PLANS, EVEN IF PROVIDED BY OTHERS, FBC 109. |
| | |
| | 5. IF THE SHUTTER INSTALLATION SCHEDULE IS NOT |
| | CORRECTED WHEN RESUBMITTED, THIS PERMIT WILL BE ISSUED |
| | WITH PROVISO THAT A REVISION WILL BE REQUIRED PRIOR TO |
| | FIRST INSPECTION, FBC 107. |
| | |
| | 6. RESUBMITTALS ARE TO BE DONE THROUGH THE FRONT |
| | COUNTER WITH A RESUBMITTAL FORM. FAILURE TO FOLLOW THE |
| | PROCEDURES MAY RESULT IN PLANS NOT BEING ROUTED AND |
| | REVIEWED TIMELY, OR IN PLANS MISPLACED OR LOST. THE |
| | RESUBMITTAL FORM AND TRACKING THROUGH THE FRONT COUNTER |
| | ENSURES THAT YOUR RESUBMITTAL IS REVIEWED AND FILED |
| | CORRECTLY AND WITHIN OUR TARGET TURNAROUND TIMES. |
| | |
| | |
| | |
| | |