| Plan Review Notes For Permit 14100100 |
| Permit Number |
14100100 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-01-23 16:41:52 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE | | | WITH THE ANCHOR CHARTS ON SHEET 11 (FOR EXAMPLE, 1 TOP, | | | 2 BOTTOM, ETC.). FOR TAPCONS, MASONRY SUBSTRATE, NOT | | | ALL CONNECTION TYPES ARE ALLOWED AND ALL REQUIRE ANCHOR | | | SPACING OF 4 1/2" OR 5". 12" IS PROPOSED. | | | | | | 2. SUBSTRATE STATED IS "CONC. BLK". MOST CBS STRUCTURES | | | HAVE A CONCRETE TOP SUBSTRATE, MASONRY BOTTOM | | | SUBSTRATE. | | | | | | 3. PLEASE RE PRINT THE SHUTTER PRODUCT APPROVALS AS | | | THEY ARE NOT LEGIBLE AND/OR COMPLETE, FBC 107. AT | | | APPEARS THAT ONLY HALF OF THE PAGE PRINTED. | | | | | | |
|