Date Text
2014-10-21 16:03:3510/21/2014
 PROJECT: 512 53RD ST
 PERMIT#:14100083
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE THE LOCATION OF ELECTRICAL PANEL WITH PANEL
 SCHEDULE INDICATING THE CIRCUIT NUMBERS FOR THE
 CIRCUITRY ON FLOOR PLAN. WPB AMENDMENTS TO FBC 107.2.1
  
 2) OUTLET BOXES OR OUTLET BOX SYSTEMS USED AS THE SOLE
 SUPPORT OF A CEILING-SUSPENDED (PADDLE) FAN SHALL BE
 LISTED, SHALL BE MARKED BY THEIR MANUFACTURER AS
 SUITABLE FOR THIS PURPOSE, AND SHALL NOT SUPPORT
 CEILING-SUSPENDED (PADDLE) FANS THAT WEIGH MORE THAN 32
 KG (70 LB) NEC314.27(D)
  
 3) RECEPTACLES SHALL BE INSTALLED SUCH THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL
 SPACE IS MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE
 OUTLET. NEC210.52(A)(1)
  
 4) WHERE A FEEDER SUPPLIES BRANCH CIRCUITS IN WHICH
 EQUIPMENT GROUNDING CONDUCTORS ARE REQUIRED, THE FEEDER
 SHALL INCLUDE OR PROVIDE AN EQUIPMENT GROUNDING
 CONDUCTOR IN ACCORDANCE WITH THE PROVISIONS OF 250.134,
 TO WHICH THE EQUIPMENT GROUNDING CONDUCTORS OF THE
 BRANCH CIRCUITS SHALL BE CONNECTED. WHERE THE FEEDER
 SUPPLIES A SEPARATE BUILDING OR STRUCTURE, THE
 REQUIREMENTS OF 250.32(B) SHALL APPLY. NEC 215.6
  
 5) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 6) INDICATE THE ELECTRICAL PROVISION FOR HOT WATER IF
 APPLICABLE. WPB AMENDMENTS TO FBC 107.2.1
  
 7) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS
 TO FBC 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  