Plan Review Notes
Plan Review Notes For Permit 14100055
Permit Number 14100055
Review Stop B
Sequence Number 2
Notes
Date Text
2014-10-31 08:27:05****PROVISO****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE A LETTER OR A REVISED PLAN FROM DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER) WHICH INCORPORATES
 MINIMUM ELEVATION OF 7'6" FOR THE NEW BAR.
  
 2. ELEVATION CERTIFICATE WHICH SHOWS THE NEW BAR AT
 7'6" TO BE PROVIDED PRIOR TO FINAL INSPECTION.
  
 3. ALL NEW MATERIALS BELOW 7'6" ARE TO COMPLY WITH FBC
 1612, FLOOD LOADS. ARCHITECT'S PLAN PROPOSES THAT
 IMPROVEMENTS WILL RESIST FLOOD LOADS AND FLOTATION, BUT
 THE PLAN DOES NOT ADDRESS FLOOD RESISTANT MATERIALS.
  
  
  
  