Plan Review Notes For Permit 14091097
Permit Number 14091097
Review Stop E
Sequence Number 1
Notes
Date Text
2014-10-01 10:34:2510/1/2014
 PROJECT: 901 FOREST HILL
 PERMIT#: 14091097
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE AN ELECTRICAL DEMOLITION FLOOR PLAN
 INDICATING THE FOLLOWING:
 A. THE LOCATION OF THE ELECTRICAL SERVICE AND BREAKER
 PANEL(S).
 B. THE ELECTRICAL CIRCUITRY TO BE REMOVED.
 C. THE LOCATIONS OF WHERE THE ELECTRICAL CIRCUITRY TO
 BE REMOVED WILL BE REMOVED TO.
  
 2) PROVIDE A NEW PROPOSED ELECTRICAL FLOOR PLAN
 IDICATING WHAT IF ANY ELECTRICAL CIRCUITRY, OUTLETS,
 AND LIGHTING THAT AREPROPOSED TO BE LEFT IN PLACE TO
 REMAIN AS IS OR TO BE INSTALLED NEW.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  