2014-09-30 04:47:56WPB AMEND. TO 2010 FBC SEC. 107.2.1, 2010 FUEL GAS CODE
 TABLES 402.4 (2), TABLE 402.4 (20), SEC.402.4.3.
  
 1) THE COPIES OF THE GAS SIZING TABLES FOR THE P.E.
 PIPE AND THE METALLIC PIPE ARE FROM THE 2004 FLORIDA
 FUEL GAS CODE WHICH IS 3 CODE CYCLES AGO. THE GAS CODE
 IN EFFECT AT THIS TIME IS THE 2010 FLORIDA FUEL GAS
 CODE.SUBMIT COPIES OF THE APPLICABLE SIZING TABLES FROM
 THE CURRENT CODE EDITION
 2) YOU IDENTIFIED THE MAXIMUM CAPACITY OF THE 3/4" SCH.
 40 GALVINIZED PIPE AS 250,000 BTU'S ON THE PLAN BUT THE
 TWO APPLIANCES ON THIS LINE ADD UP TO 364,000 BTU'S SO
 THE 3/4" SIZE WILL NOT MEET THE DEMAND. THE LINE NEEDS
 TO BE 1".
 3) SHOW THE LOCATION OF THE SECOND STAGE REGULATOR ON
 THE RISER DIAGRAM.
  