Plan Review Notes
Plan Review Notes For Permit 14091026
Permit Number 14091026
Review Stop B
Sequence Number 2
Notes
Date Text
2014-10-06 18:39:43RESIDENTIAL (R2) FLOORING SECOND BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- ASTM E 84 TEST SUBMITTED FOR THE FLAME SPREAD INDEX
 AND SMOKE DEVELOPED INDEX IS FOR PROFLEX MSC 90. THE
 INFORMATION PREVIOUSLY SUBMITTED FOR THE IMPACT
 INSULATION CLASS (IIC) AND SOUND TRANSMISSION CLASS
 (STC) IS FOR SAM TM 3 90. THESE ARE TWO DIFFERENT
 PRODUCTS. PLEASE PROVIDE COMPLETE INFORMATION FOR ONE
 PRODUCT.
  
 ***NOTE: CHECK THE IIC AND STC TESTS FOR THE PROFLEX
 MSC 90. TYPICALLY THIS TEST IS DONE WITH A FLOOR
 ASSEMBLY CONSISTING OF 8" CONCRETE SLAB WITH A
 SUSPENDED CEILING. IF THE PROPOSED INSTALLATION MATCHES
 THIS FLOOR ASSEMBLY THEN IT WILL BE OK. OTHERWISE,
 ANOTHER PRODUCT MAY NEED TO BE USED.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]