| Plan Review Notes For Permit 14091024 |
| Permit Number |
14091024 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-12-09 16:03:05 | NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW | | | COMMENTS. | | | CODE: 2010 FBC | | | | | | 1- NEW EQUIPMENT SIZING CALCULATIONS WERE PROVIDED. NEW | | | CALCULATIONS ARE MISSING THE WORKSHEET FOR ENTIRE | | | HOUSE. OLD CALCULATIONS ARE DONE FOR WORST CASE | | | SCENARIO (NE, SE, SW AND NW). THIS IS NOT ALLOWED. THE | | | EQUIPMENT SIZING CALCULATIONS NEED TO BE REVISED. THEY | | | NEED TO BE DONE BASED ON THE ACTUAL BUILDING | | | ORIENTATION OF THE HOUSE AS REQUIRED BY SEC. 403.6 OF | | | 2010 FBC-ENERGY CONSERVATION. PROVIDE TWO COMPLETE | | | REVISED EQUIPMENT SIZING CALCULATIONS. | | | | | | 2- A/C PLAN: | | | A) PROVIDE THE NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. 107.2.1 | | | OF CITY AMENDMENTS TO FBC. | | | | | | B) PROVIDE THE EQUIPMENT INFORMATION ON THE A/C PLAN AS | | | REQUIRED BY SEC. 107.3.5.3(10) OF CITY AMENDMENTS. | | | ***NOTE: COORDINATE WITH EQUIPMENT SPECIFIED ON THE | | | REVISED EQUIPMENT SIZING CALCULATIONS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] | | | | | | |
|