| Date |
Text |
| 2014-12-11 09:33:59 | 12/11/2014 |
| | PROJECT: 307 PURITAN RD |
| | PERMIT#: 14091024 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED. |
| | |
| | 1) FBC, WPB AMENDMENTS 107.2.1 |
| | A. ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. THE ELECTRICAL |
| | PLANS, SHEET E1 ARE NOT SIGNED OR SEALED. |
| | FL SS 471, AND FL SS 668.001- 668.006 |
| | B. ALL FINAL DRAWINGS, SPECIFICATIONS, PLANS, REPORTS, |
| | OR DOCUMENTS PREPARED OR ISSUED BY THE LICENSEE AND |
| | BEING FILED FOR PUBLIC RECORD AND ALL FINAL DOCUMENTS |
| | PROVIDED TO THE OWNER OR THE OWNER?S REPRESENTATIVE |
| | SHALL BE SIGNED BY THE LICENSEE, DATED, AND SEALED WITH |
| | SAID SEAL. THE ELECTRICAL PLANS, SHEET E1ARE NOT SIGNED |
| | OR SEALED. |
| | |
| | 2) NEC 110.9 |
| | VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS HAS A |
| | FAULT CURRENT RATING THAT IS SUFFICIENT AT NOMINAL |
| | CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| | INTERRUPTED. |
| | |
| | 3) NEC 210.23 (2) UTILIZATION EQUIPMENT FASTENED IN |
| | PLACE. |
| | THE TOTAL RATING OF UTILIZATION EQUIPMENT FASTENED IN |
| | PLACE, OTHER THAN LUMINAIRES, SHALL NOT EXCEED 50 |
| | PERCENT OF THE BRANCHCIRCUIT AMPERE RATING. THE |
| | DISHWASHER AND DISPOSAL CAN NOT SHARE A CIRCUIT UNLESS |
| | PROOF AND BE SHOWN THAT NEITHER APPLIANCE WILL EXCEED |
| | 50% OF THECRATED LOAD OF THE BRANCH CIRCUIT. |
| | |
| | 4) NEC 210.52(E)(3) |
| | FOR A ONE FAMILY DWELLING AND EACH UNIT OF A TWO-FAMILY |
| | DWELLING THAT IS AT GRADE LEVEL, AT LEAST ONE |
| | RECEPTACLE OUTLET ACCESSIBLE WHILE STANDING AT GRADE |
| | LEVEL AND LOCATED NOT MORE THAN 2.0 M (61.2 FT) ABOVE |
| | GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE |
| | DWELLING. INDICATE THE REQUIRED GFI OUTLET AT TH THE |
| | FRONT OF THE RESIDENCE. |
| | |
| | 5) NEC 210.12, 406.11 |
| | ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| | RESISTANT AND AFCI PROTECTED. |
| | |
| | 6) NEC 210.8. |
| | ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES |
| | INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8) |
| | SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION |
| | FOR PERSONNEL. ALL OUTLETS IN THE GARAGE SHALL BE GFCI |
| | PROTECTED. |
| | |
| | 7) NEC 408.4 |
| | EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY |
| | IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC |
| | PURPOSE OR USE. PROVIDE THE REQUIRED OCPD IN THE PANEL |
| | FOR THE A/C CONDENSING UNIT. THE CIRCUIT CURRENTLY |
| | LISTED FOR THE A/C CU IS INDICATED ON THE FLOOR PLN AS |
| | THE DRYER CIRCUIT. INDIACTE THE REQUIERD OCPD FOR THE |
| | DRYER CIRCUIT AS WELL. |
| | |
| | 8) NEC 220.16(2). |
| | LOADS FOR NEW CIRCUITS OR EXTENDED CIRCUITS IN |
| | PREVIOUSLY WIRED DWELLING UNITS SHALL BE CALCULATED IN |
| | ACCORDANCE WITH EITHER 220.12 OR 220.14, AS |
| | APPLICABLE.CORRECT THE LOAD CALCULATION TO INCLUDE THE |
| | REQUIRED 5KW LOAD FOR THE DRYER. |
| | |
| | 9) NEC 210.63 SEE 210.8(A)(3), |
| | ONE 125VOLT, SINGLE-PHASE, 15 OR 20AMP GFI RECEPTACLE |
| | OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR |
| | THE SERVICING OF HEATING, AIR-CONDITIONING, AND |
| | REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE |
| | LOCATED ON THE SAME LEVEL AND WITHIN 25FT OF THE |
| | HEATING, AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. |
| | THE RECEPTACLE OUTLET SHALL NOT BE CONNECTED TO THE |
| | LOAD SIDE OF THE EQUIPMENT DISCONNECTING MEANS. |
| | |
| | 10) NEC 210.52 (A) GENERAL PROVISIONS. IN EVERY |
| | KITCHEN, FAMILY ROOM, DINING ROOM, LIVING ROOM, PARLOR, |
| | LIBRARY, DEN, SUNROOM, BEDROOM, RECREATION ROOM, OR |
| | SIMILAR ROOM OR AREA OF DWELLING UNITS, RECEPTACLE |
| | OUTLETS SHALL BE INSTALLED IN ACCORDANCE WITH THE |
| | GENERAL PROVISIONS SPECIFIED IN 210.52(A)(1) THROUGH |
| | (A)(3). VERIFY SPACING THROUGHOUT. |
| | |
| | 11) 210.70(A)(3) |
| | PROVIDE A LIGHTING OUTLET AND SWITCH FOR WHAT APPEARS |
| | TO BE A SECONDARY ATTIC ACCESS IN MASTER CLOSET. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |