| 2014-12-08 18:15:22 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- SOIL TEST REPORT FOOTING RECOMMENDATIONS CALL FOR 40 |
| | INCH-WIDE SQUARE FOOTINGS. SIZE OF FOOTINGS SHOWN ON |
| | PLANS ARE SMALLER. ENGINEER OF RECORD TO REVIEW SOIL |
| | TEST REPORT AND DETERMINE IF FOOTING SIZE SPECIFIED ON |
| | PLANS IS ADEQUATE EVEN AFTER REVIEWING THE SOIL TEST |
| | REPORT. SEC. 107.2.1.3 OF CITY AMENDMENTS TO FBC. |
| | |
| | 2- WALL SECTIONS ON SHEET S1: REVISE SPECIFICATIONS FOR |
| | THE HIGH RIBBED METAL LATH ATTACHMENT. REVISE THE NAIL |
| | SIZE TO SHOW COMPLIANCE WITH ASTM C1063 SEC. 7.10.2.3. |
| | |
| | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) OVERHEAD GARAGE DOOR THAT MEETS THE DESIGN PRESSURES |
| | CALCULATED BY THE ENGINEER. AND, NEED TO PROVIDE |
| | CURRENT NOA BECAUSE NOA 11-0414.12 SUBMITTED WAS |
| | SUPERSEDED BY MIAMI-DADE. |
| | B) ROOF TILE FOAM. NOA 12-0228.18 SUBMITTED WAS |
| | SUPERSEDED BY MIAMI-DADE. NEED CURRENT NOA. |
| | |
| | 4- DESIGN PROFESSIONAL OF RECORD TO REVIEW AND APPROVE |
| | ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 |
| | OF CITY AMENDMENTS. |
| | |
| | 5- ENERGY CALCULATIONS: |
| | A) REVISE DOORS INFORMATION ON SHEET 3 OF 5. THERE ARE |
| | NOT WOOD WOOD DOORS. SEE PLANS AND PRODUCT APPROVALS |
| | SUBMITTED. SEC. 103.2.1.1.2 OF 2010 FBC-ENERGY |
| | CONSERVATION. |
| | B) REVISE ORIENTATION OF WALLS, DOORS AND WINDOWS TO |
| | MATCH ACTUAL ORIENTATION SHOWN ON THE SURVEY. SEC. |
| | 103.2.1.1.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | C) COORDINATE HEATING AND COOLING INFORMATION WITH |
| | REVISED EQUIPMENT SIZING CALCULATIONS. (SEE MECHANICAL |
| | REVIEW COMMENTS DATED 12/9/14). |
| | |
| | 6- PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE |
| | WINDOWS AND DOORS SHOWING COMPLIANCE WITH THE U-FACTOR |
| | AND SHGC FACTOR SPECIFIED IN THE ENERGY CALCULATIONS IN |
| | ITEM #7. REQUIRED BY SEC. 103.2.2 OF 2010 FBC-ENERGY |
| | CONSERVATION. |
| | |