| Plan Review Notes For Permit 14091024 |
| Permit Number |
14091024 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-10-22 07:03:38 | 1) THE AAV (STUDOR VENT) SHALL CONNECT A MINIMUM OF 4" | | | ABOVE THE HORIZONTAL BRANCH DRAIN PER 2010 FBCR, | | | SEC.P3114.4. | | | 2) A VENT IS REQD. BETWEEN THE WATER CLOSET & BIDET IN | | | THE M.B. 2010 FBCR, SEC.P3101.2. | | | 3) THE LAYOUT OF BATH #2 ON THE RISER DOES NOT MATCH | | | THE FLOOR PLAN. | | | 4) CLEANOUTS ARE REQD. IN ALL STACKS. 2010 FBCR SEC.P | | | 3005.2.6. | | | 5) IS THERE A DRAIN LOCATED IN THE OUTSIDE SHOWER? IF | | | SO , SHOW IT ON THE SANITARY RISER. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|