| Plan Review Notes For Permit 14091021 |
| Permit Number |
14091021 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2014-10-30 14:21:19 | PASS PROVISO | | | PROVIDE A DETAIL FROM THE ENGINEER ON CURB TO ROOF TIE | | | DOWN | | | AND RTU TO CURB TIE DOWN. PROVIDE BOLT SIZE ON THE | | | DETAIL. | | | PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M) | | | | | | REFER TO SECTION 1509.7 MECHANICAL UNITS FOR HIGHT OF | | | CURB | | | 2010 FBC. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|