2014-10-30 14:21:19 | PASS PROVISO | | PROVIDE A DETAIL FROM THE ENGINEER ON CURB TO ROOF TIE | | DOWN | | AND RTU TO CURB TIE DOWN. PROVIDE BOLT SIZE ON THE | | DETAIL. | | PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M) | | | | REFER TO SECTION 1509.7 MECHANICAL UNITS FOR HIGHT OF | | CURB | | 2010 FBC. | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|