| 2014-10-03 18:56:10 | PLAN REVIEW COMMENTS | | | | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | ELECTRICAL | | | | | | 1) ON SHEET P-2 UNDER EQUIPMENT SELECTION IS LISTED " | | | HEATER (ELECTRIC): JANDY 400 BTU GAS " . PLEASE CLARIFY | | | IF THE POOL HEATER WILL BE GAS OR ELECTRIC AND CORRECT | | | THE NOTE ACCORDINGLY. FBC 107.2.1 | | | | | | 2) IF THE POOL HEATER IS ELECTRIC, SUBMIT LOAD | | | CALCULATIONS TO SHOW THAT THE EXISTING SERVICE WILL | | | ACCOMMODATE THE NEW HEAT PUMP. NEC 220.40 | | | | | | 3) IF THE POOL HEATER IS ELECTRIC, SUBMIT THE CUT | | | SHEETS WITH THE ELECTRIC REQUIREMENTS FOR THE POOL | | | HEATER. NEC 680.9 | | | | | | | | | |
|