| Notes |
| Date |
Text |
| 2014-12-01 10:11:30 | 1) SUBMIT SIZING CALCULATIONS TO SHOW THAT THE SIZE OF | | | THE THERMACO GREASE REMOVAL DEVICE IS ADEQUATE TO | | | HANDLE THE AMOUNT OF GREASE THAT WILL BE PRODUCED. THE | | | GREASE REMOVAL DEVICE SHALL BE SIZED IN ACCORDANCE W/ | | | 2010 FPC SEC.1003.3.4, 1003.3.5. 4TH. REQUEST. USE THE | | | SIZING METHOD FOR FIGURING THE FLOW RATE FROM PDI G101. | | | YOU MUST CALCULATE THE GPM FLOW OF THE 3 COMPARTMENT | | | SINK AND FIGURE THE PEAK FLOW RATE. ONCE THE PEAK GPM | | | FLOWRATE IS CALCULATED AND PLACED ON THE PLANS I CAN | | | THEN COMPARE THAT PEAK FLOW AGAINST THE PEAK FLOW RATE | | | OF THE THERMACO GREASE TRAP (20 GPM) TO SEE IF THE | | | GREASE TRAP IS LARGE ENOUGH. | | | 2) CONSTRUCTION DOCUMENTS SHALL BE SUBMITTED IN TWO OR | | | MORE SETS WITH EACH PERMIT APPLICATION PER WPB AMEND. | | | TO 2010 FBC SEC.107.1.BOTH COPIES OF THE PLANS SHALL BE | | | SIGNED AND SEALED BY THE DESIGN PROFESSIONAL OF RECORD | | | PER THE FL. ADMIN. CODE RULE 61G15-23.002. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|