Plan Review Notes
Plan Review Notes For Permit 14090960
Permit Number 14090960
Review Stop P
Sequence Number 3
Notes
Date Text
2014-11-25 06:47:111) SUBMIT SIZING CALCULATIONS TO SHOW THAT THE SIZE OF
 THE THERMACO GREASE REMOVAL DEVICE IS ADEQUATE TO
 HANDLE THE AMOUNT OF GREASE THAT WILL BE PRODUCED. THE
 GREASE REMOVAL DEVICE SHALL BE SIZED IN ACCORDANCE W/
 2010 FPC SEC.1003.3.4, 1003.3.5. 3RD. REQUEST.
 2) CLEARLY SHOW THE REQUIRED 60" X 56" CLEARANCE FOR
 THE WATER CLOSET IN THE NEW ACCESSIBLE BATHROOM.PER THE
 FAC SEC.604.3.1. 3RD REQUEST.
 3) SHOW THE LOCATION OF THE WATER HEATER ON THE FLOOR
 PLAN. 2ND REQUEST
 4) THE WATER HEATER DETAIL SHOWS AN EXHAUST ON THE
 HEATER. THE DETAIL ALSO NOTES A THERMAL EXPANSION TANK
 AND NOTHING IS SHOWN. THE DETAIL SHOWS A PRESSURE
 RELIEF VALVE IN TWO DIFFERENT LOCATIONS ON THE WATER
 HEATER DETAIL. CLARIFY.
 5) SUBMIT A LEGEND FOR THE PLUMBING ITEMS NUMBERED P1,
 P2 ,P3, ETC. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  