| Plan Review Notes For Permit 14090960 |
| Permit Number |
14090960 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-10-14 08:59:17 | WPB ADMIN. AMEND. TO 2010 FBC SEC. 107.2.1. | | | 1) SHT. A-1 REFERS TO A SURFACE MOUNT GREASE TRAP. | | | SUBMIT MANUFACTURER'S SPECS AND INSTALLATION | | | INSTRUCTIONS FOR THE UNIT. | | | 2) PROVIDE INFORMATION AS TO WHAT TYPE OF FOOD WILL BE | | | PREPARED AND HOW IT IS GOING TO BE COOKED. | | | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS / INSTALLATION | | | INSTRUCTIONS FOR THE INSTA-HOT. | | | 4) THE DESIGN PROFESSIONAL OF RECORD HAS CLASSIFIED | | | THIS SPACE AS A MERCANTILE OCCUPANCY, THEREFORE A | | | DRINKING FOUNTAIN IS REQUIRED PER TABLE 403.1 OF THE | | | 2010 FBC. A MINIMUM OF TWO DRINKING FOUNTAINS ARE | | | REQUIRED PER THE 2010 FBC, ACCESSIBILITY, SEC. 211.2. | | | 5) SUBMIT CALCULATIONS FOR THE SIZING OF THE GREASE | | | REMOVAL DEVICE. CALCULATIONS SHALL BE BASED ON THE | | | CRITERIA SET FORTH IN 2010 FBC, PLUMBING, SECS. | | | 1003.3.1, 1003.3.4, 1003.3.5. | | | 6) THE NEW ACCESSIBLE BATHROOM SHALL COMPLY WITH THE | | | 2010 FBC ACCESSIBILITY CODE. THE CLEARANCE AROUND A | | | WATER CLOSET SHALL BE 60 INCHES MINIMUM MEASURED | | | PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES MINIMUM | | | MEASURED PERPENDICULAR FROM THE REAR WALL PER SEC. | | | 604.3.1 OF THE ACCESSIBILITY CODE. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|