| Plan Review Notes For Permit 14090960 |
| Permit Number |
14090960 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-10-07 16:30:41 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | THE DOORS TO THE OFFICE AND RESTROOM ENCROACH INTO THE | | | EXIT CORRIDOR. PER CHAPTER 7 OF NFPA 101, DURING ITS | | | SWING, ANY DOOR LEAF IN A MEANS OF EGRESS SHALL LEAVE | | | NOT LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF AN | | | AISLE, A CORRIDOR, A PASSAGEWAY, OR A LANDING | | | UNOBSTRUCTED AND SHALL NOT PROJECT NOT MORE THAN 7 IN. | | | INTO THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A | | | PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN. | | | | | | THE PLANS INDICATE "NO OPEN FLAME"; HOWEVER, PLEASE | | | PROVIDE THE TYPE OF FOOD PREPRATIONS THAT WILL TAKE | | | PLACE. ANY FOOD PREPARATIONS PRODUCING GREASE LAYDEN | | | VAPORS SHALL REQUIRE A HOOD VENTILATION AND FIRE | | | SUPRRESSION SYSTEM. | | | | | | WILL THERE BE SEATING AT THIS OCCUPANCY? PLEASE | | | INDICATE ON THE PLANS "NO SEATING" OR PROVIDE A SEAT | | | PROPOSED PLAN. | | | |
|