Plan Review Notes
Plan Review Notes For Permit 14090960
Permit Number 14090960
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-10-07 16:30:41THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE DOORS TO THE OFFICE AND RESTROOM ENCROACH INTO THE
 EXIT CORRIDOR. PER CHAPTER 7 OF NFPA 101, DURING ITS
 SWING, ANY DOOR LEAF IN A MEANS OF EGRESS SHALL LEAVE
 NOT LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF AN
 AISLE, A CORRIDOR, A PASSAGEWAY, OR A LANDING
 UNOBSTRUCTED AND SHALL NOT PROJECT NOT MORE THAN 7 IN.
 INTO THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A
 PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN.
  
 THE PLANS INDICATE "NO OPEN FLAME"; HOWEVER, PLEASE
 PROVIDE THE TYPE OF FOOD PREPRATIONS THAT WILL TAKE
 PLACE. ANY FOOD PREPARATIONS PRODUCING GREASE LAYDEN
 VAPORS SHALL REQUIRE A HOOD VENTILATION AND FIRE
 SUPRRESSION SYSTEM.
  
 WILL THERE BE SEATING AT THIS OCCUPANCY? PLEASE
 INDICATE ON THE PLANS "NO SEATING" OR PROVIDE A SEAT
 PROPOSED PLAN.
  