Plan Review Notes
Plan Review Notes For Permit 14090954
Permit Number 14090954
Review Stop E
Sequence Number 1
Notes
Date Text
2014-10-17 16:29:2010/17/2014
 PROJECT: 1578 6TH ST
 PERMIT#: 14090954
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) INDICATE ALL KITCHEN COUNTER TOP RECEPTACLES TO BE
 GFCI PROTECTED. NEC 210.8
  
 2) IN KITCHENS, AND SIMILAR AREAS OF DWELLING UNITS,
 RECEPTACLE OUTLETS FOR COUNTERTOP SPACES SHALL BE
 INSTALLED IN ACCORDANCE WITH NEC 210.52(C)(1) THROUGH
 (C)(5).
  
 3) AT LEAST ONE RECEPTACLE SHALL BE INSTALLED AT EACH
 ISLAND COUNTERTOP SPACE WITH A LONG DIMENSION OF 12" OR
 GREATER AND A SHORT DIMENSION OF 12" OR GREATER. NEC
 210.52 (C)(2)
  
 4) PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE
 BATHROOMS. NEC 210.11 (C)(3)
  
 5) THE SIZE OF THE GROUNDING ELECTRODE CONDUCTOR AT THE
 SERVICE, AT EACH BUILDING OR STRUCTURE WHERE SUPPLIED
 BY A FEEDER(S) OR BRANCH CIRCUIT(S), OR AT A SEPARATELY
 DERIVED SYSTEM OF A GROUNDED OR UNGROUNDED AC SYSTEM
 SHALL NOT BE LESS THAN GIVEN IN TABLE 250.66, EXCEPT AS
 PERMITTED IN NEC 250.66(A) THROUGH (C).
  
 6) ALL GROUNDING ELECTRODES AS DESCRIBED IN
 250.52(A)(1) THROUGH (A)(7) THAT ARE PRESENT AT EACH
 BUILDING OR STRUCTURE SERVED SHALL BE BONDED TOGETHER
 TO FORM THE GROUNDING ELECTRODE SYSTEM. WHERE NONE OF
 THESE GROUNDING ELECTRODES EXIST, ONE OR MORE OF THE
 GROUNDING ELECTRODES SPECIFIED IN 250.52(A)(4) THROUGH
 (A)(8) SHALL BE INSTALLED AND USED. NEC 250.50
  
 7) LUMINAIRES IN CLOTHES CLOSETS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE PROVISIONS OF THE NEC 410.16(A) AND
 (B).
  
 8) INDICATE CIRCUITRY ON PLANS TO CORRESPOND TO
 CIRCUITS ON PANEL SCHEDULE. WPB AMENDMENTS TO FBC
 107.2.1
  
 9) CLARIFY THE INDICATION AND USE FOR THE "100AMP
 BREAKER FOR "LT" SHOWN ON THE ELECTRICAL RISER DIAGRAM.
 WPB AMENDMENTS TO FBC 107.2.1
  
 10) SMOKE DETECTORS ARE REQUIRED PER FBC-R 314 IF THE
 RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A
 FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC-R
 R315
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved