| Date |
Text |
| 2014-10-17 16:29:20 | 10/17/2014 |
| | PROJECT: 1578 6TH ST |
| | PERMIT#: 14090954 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) INDICATE ALL KITCHEN COUNTER TOP RECEPTACLES TO BE |
| | GFCI PROTECTED. NEC 210.8 |
| | |
| | 2) IN KITCHENS, AND SIMILAR AREAS OF DWELLING UNITS, |
| | RECEPTACLE OUTLETS FOR COUNTERTOP SPACES SHALL BE |
| | INSTALLED IN ACCORDANCE WITH NEC 210.52(C)(1) THROUGH |
| | (C)(5). |
| | |
| | 3) AT LEAST ONE RECEPTACLE SHALL BE INSTALLED AT EACH |
| | ISLAND COUNTERTOP SPACE WITH A LONG DIMENSION OF 12" OR |
| | GREATER AND A SHORT DIMENSION OF 12" OR GREATER. NEC |
| | 210.52 (C)(2) |
| | |
| | 4) PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE |
| | BATHROOMS. NEC 210.11 (C)(3) |
| | |
| | 5) THE SIZE OF THE GROUNDING ELECTRODE CONDUCTOR AT THE |
| | SERVICE, AT EACH BUILDING OR STRUCTURE WHERE SUPPLIED |
| | BY A FEEDER(S) OR BRANCH CIRCUIT(S), OR AT A SEPARATELY |
| | DERIVED SYSTEM OF A GROUNDED OR UNGROUNDED AC SYSTEM |
| | SHALL NOT BE LESS THAN GIVEN IN TABLE 250.66, EXCEPT AS |
| | PERMITTED IN NEC 250.66(A) THROUGH (C). |
| | |
| | 6) ALL GROUNDING ELECTRODES AS DESCRIBED IN |
| | 250.52(A)(1) THROUGH (A)(7) THAT ARE PRESENT AT EACH |
| | BUILDING OR STRUCTURE SERVED SHALL BE BONDED TOGETHER |
| | TO FORM THE GROUNDING ELECTRODE SYSTEM. WHERE NONE OF |
| | THESE GROUNDING ELECTRODES EXIST, ONE OR MORE OF THE |
| | GROUNDING ELECTRODES SPECIFIED IN 250.52(A)(4) THROUGH |
| | (A)(8) SHALL BE INSTALLED AND USED. NEC 250.50 |
| | |
| | 7) LUMINAIRES IN CLOTHES CLOSETS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH THE PROVISIONS OF THE NEC 410.16(A) AND |
| | (B). |
| | |
| | 8) INDICATE CIRCUITRY ON PLANS TO CORRESPOND TO |
| | CIRCUITS ON PANEL SCHEDULE. WPB AMENDMENTS TO FBC |
| | 107.2.1 |
| | |
| | 9) CLARIFY THE INDICATION AND USE FOR THE "100AMP |
| | BREAKER FOR "LT" SHOWN ON THE ELECTRICAL RISER DIAGRAM. |
| | WPB AMENDMENTS TO FBC 107.2.1 |
| | |
| | 10) SMOKE DETECTORS ARE REQUIRED PER FBC-R 314 IF THE |
| | RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A |
| | FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED |
| | WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC-R |
| | R315 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |