| 2014-10-10 10:09:50 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. FBC 2010 ACCESSIBLITY, 221.1, 903: IT APPEARS THAT |
| | THE PROPOSED RETAINING WALL/PLANTER HAS A DUAL PURPOSE, |
| | SERVING AS A BENCH FOR RESTING AND SPECTATING. SEE |
| | SECTION 903; BENCH HEIGHT COMPLIES WITH ACCESSIBLITY |
| | REQUIREMENTS BUT NO BACK SUPPORTS SHOWN. EITHER REVISE |
| | TO COMPLY WITH SECTION 903 AND SHOW LOCATION(S), OR |
| | PROVIDE RATIONALE FOR NOT PROVIDING ACCESSIBLE BENCHES. |
| | IF BENCH BACKS ARE NOT ADDED, PLEASE CONTACT ME PRIOR |
| | TO RESUBMITTAL TO DISCUSS. |
| | |
| | 2. FBC 1612.1, THE PROPOSED IMPROVEMENT IS LOCATED IN A |
| | SPECIAL HAZARD FLOOR AREA. NO ELEVATIONS WERE PROVIDED |
| | ON THE SITE PLAN. |
| | |
| | IF THE PROPOSED IMPROVEMENT IS ENTIRELY ABOVE THE |
| | DESIGN FLOOD ELEVATION REQUIRED, (BFE PLUS FREEBOARD OF |
| | 6"), RESISTANCE TO FLOOD LOADS IS NOT REQUIRED. |
| | |
| | IF THE PROPOSED IMPROVEMENT IS BELOW THE DESIGN FLOOD |
| | ELEVATION, REVISE THE PLAN TO DEMONSTRATE THAT THE WALL |
| | HAS BEEN DESIGNED TO RESIST THE EFFECTS OF FLOOD |
| | HAZARDS AND FLOOD LOADS. AS THIS IS A RETAINING WALL, |
| | IT IS NOT CLEAR WHETHER THE ISSUE OF SATURATION HAS |
| | BEEN CONSIDERED IN THE DESIGN. |
| | |
| | REVISE PLAN OR SITE PLAN TO INCLUDE ELEVATIONS. IF |
| | FLOOD RESISTANCE IS REQUIRED, REVISE PLAN TO INCLUDE |
| | DESIGN CRITERIA. |
| | |
| | 3. FBC 1603.1.4, REVISE PLAN TO INCLUDE WIND DESIGN |
| | CRITERIA. |
| | |
| | |
| | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: |
| | |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | SWAP OUT SHEETS WHICH HAVE CHANGED SO THAT THERE ARE |
| | TWO COMPLETE, COLLATED PLANS READY FOR PERMIT ISSUANCE. |
| | OLD SHEETS ARE TO BE RETAINED IN THE PERMIT APPLICATION |
| | PACKAGE (SEPARATE FROM THE PERMIT SETS) AND MARKED *OLD |
| | SHEETS* OR *VOID*. |
| | |
| | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS |
| | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. |
| | |