| 2014-10-06 14:14:00 | 10/6/2014 | | | PROJECT: PALM BEACH ZOO TIIGER EXHIBIT | | | PERMIT#: 14090945 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | 1) NO ELECTRICAL PLANS OR SPECIFICATIONS HAVE BEEN | | | PROVIDED WITH THIS SUBMITTAL. PROVIDE THE FOLLOWING | | | MINIMUM PLNA REVIEW CRITERA AS DIECTED BY THE WPB | | | AMENDMENTS TO THE FBC 107.3.5.1.2 ELECTRICAL: | | | WIRING | | | SERVICES | | | FEEDERS AND BRANCH CIRCUITS | | | OVERCURRENT PROTECTION | | | GROUNDING | | | WIRING METHODS AND MATERIALS | | | GFCIS | | | 2. EQUIPMENT | | | 3. SPECIAL OCCUPANCIES | | | 4. EMERGENCY SYSTEMS | | | 5. COMMUNICATION SYSTEMS IF ANY | | | 6. LOW VOLTAGE IF ANY. | | | 7. LOAD CALCULATIONS | | | 8. DESIGN FLOOD ELEVATION | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | | SHEETS FOR COMPARATIVE REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|