| 2014-10-16 11:33:34 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | THE PLANS WERE SMALL AND MANY OF THE DIMENSIONS WERE | | | UNREADALBE. MUCH OF THE WORDING WAS A IN SMALL FONT AND | | | UNREADABLE. | | | | | | THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE | | | FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND | | | COMPLIANCE. | | | | | | THE FOLLOWING MUST BE INDICATED ON THE SUBMITTAL. | | | | | | THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | | CONSTRUCTION PERIOD. | | | | | | ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER | | | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND | | | BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | | | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, | | | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE | | | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL | | | AND COMPLETE PROTECTION IS RETURNED | | | |
|