Plan Review Notes
Plan Review Notes For Permit 14090929
Permit Number 14090929
Review Stop B
Sequence Number 2
Notes
Date Text
2015-03-20 13:18:02BUILDING PLAN REVIEW
 PERMIT: 14090929
 ADD: 222 LAKEVIEW AVE. SUITE # 120
 CONT: GREEN CORPORATION
 TEL: (305)670-1000
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: FRI. MARCH 20/ 2015
 ACTION: DENIED
  
 1) COMPLIED. .
  
 2) COMPLIED.
  
 3) 2ND REQUEST. A LETTER FROM THE QUALIFIER OF BOTH THE
 ELEVATOR SHAFT CONTRACTOR (FASTRACK CORPORATION) AND
 TENANT BUILD-OUT CONTRACTOR MUST BE PROVIDED 7) BEFORE
 TENANT BUILD-OUT PERMIT CAN BE ISSUED, IF THE TENANT
 BUILD-OUT CONTRACTOR WISHES TO START WORK BEFORE THE
 ELEVATOR SHAFT HAS RECEIVED A CERTIFICATE OF
 COMPLETION, AGREEING THEY WILL WORK TOGETHER TO ACHIEVE
 CODE COMPLIANCE. THESE DOCUMENTS WILL NEED TO BE SIGNED
 BY THE QUALIFIER . PLEASE PROVIDE THE PERMIT NUMBER,
 ADDRESS WITH SUITE NUMBER WITHIN THE DOCUMENT.
  
 4) 2ND REQUEST. THE EXCEPTION FOR A WATER CURTAIN IS
 FOR THE GLAZED WALL SYSTEM UNDER 404.6. THE REQUIREMENT
 FOR SMOKE CONTROL IS UNDER SECTION 404.5 AND HAS
 NOTHING TO DO WITH THE REQUIREMENTS OF 404.6 ENCLOSURES
 AT ATRIUMS.
  
 COMMENT FROM 1ST REVIEW. THE MAIN DOUBLE ENTRY DOORS TO
 THIS TENANT SPACE ARE WITHIN AN ATRIUM AND WILL NEED TO
 BE (CORRECTION) 45 MINUTE FIRE RATED DOORS. 2010 FBC-B
 404.6 ENCLOSURE OF ATRIUMS. ATRIUM SPACES SHALL BE
 SEPARATED FROM ADJACENT SPACES BY A 1-HOUR FIRE BARRIER
 CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR A
 HORIZONTAL ASSEMBLY CONSTRUCTED IN ACCORDANCE WITH
 SECTION 712, OR BOTH. PLEASE SEE EXCEPTION # 3 FOR AN
 ACTIVE SMOKE CONTROL SYSTEM FOR THE ATRIUM.
  
 IN REVIEW
  
 5A-B) COMPLIED.
  
 6) 2ND REQUEST. PLEASE REVIEW 2010 FBC-B 404.6
 ENCLOSURES OF ATRIUMS REQUIRE A 1 HOUR FIRE BARRIER
 CONSTRUCTION.
 COMMENT FROM 1ST REVIEW. EGRESS DOOR LABELED (I) IS
 INDICATED AS A "B" LABEL DOOR IN SCHEDULE, PLEASE REFER
 TO 2010 FBC-B TABLE 715.4 FIRE BARRIERS OF 1 HR REQUIRE
 A 45 MINUTE RATED FIRE DOOR, NOT A 20 MINUTE DOOR.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved