| Date |
Text |
| 2015-03-20 13:18:02 | BUILDING PLAN REVIEW |
| | PERMIT: 14090929 |
| | ADD: 222 LAKEVIEW AVE. SUITE # 120 |
| | CONT: GREEN CORPORATION |
| | TEL: (305)670-1000 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2ND REVIEW |
| | DATE: FRI. MARCH 20/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. . |
| | |
| | 2) COMPLIED. |
| | |
| | 3) 2ND REQUEST. A LETTER FROM THE QUALIFIER OF BOTH THE |
| | ELEVATOR SHAFT CONTRACTOR (FASTRACK CORPORATION) AND |
| | TENANT BUILD-OUT CONTRACTOR MUST BE PROVIDED 7) BEFORE |
| | TENANT BUILD-OUT PERMIT CAN BE ISSUED, IF THE TENANT |
| | BUILD-OUT CONTRACTOR WISHES TO START WORK BEFORE THE |
| | ELEVATOR SHAFT HAS RECEIVED A CERTIFICATE OF |
| | COMPLETION, AGREEING THEY WILL WORK TOGETHER TO ACHIEVE |
| | CODE COMPLIANCE. THESE DOCUMENTS WILL NEED TO BE SIGNED |
| | BY THE QUALIFIER . PLEASE PROVIDE THE PERMIT NUMBER, |
| | ADDRESS WITH SUITE NUMBER WITHIN THE DOCUMENT. |
| | |
| | 4) 2ND REQUEST. THE EXCEPTION FOR A WATER CURTAIN IS |
| | FOR THE GLAZED WALL SYSTEM UNDER 404.6. THE REQUIREMENT |
| | FOR SMOKE CONTROL IS UNDER SECTION 404.5 AND HAS |
| | NOTHING TO DO WITH THE REQUIREMENTS OF 404.6 ENCLOSURES |
| | AT ATRIUMS. |
| | |
| | COMMENT FROM 1ST REVIEW. THE MAIN DOUBLE ENTRY DOORS TO |
| | THIS TENANT SPACE ARE WITHIN AN ATRIUM AND WILL NEED TO |
| | BE (CORRECTION) 45 MINUTE FIRE RATED DOORS. 2010 FBC-B |
| | 404.6 ENCLOSURE OF ATRIUMS. ATRIUM SPACES SHALL BE |
| | SEPARATED FROM ADJACENT SPACES BY A 1-HOUR FIRE BARRIER |
| | CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR A |
| | HORIZONTAL ASSEMBLY CONSTRUCTED IN ACCORDANCE WITH |
| | SECTION 712, OR BOTH. PLEASE SEE EXCEPTION # 3 FOR AN |
| | ACTIVE SMOKE CONTROL SYSTEM FOR THE ATRIUM. |
| | |
| | IN REVIEW |
| | |
| | 5A-B) COMPLIED. |
| | |
| | 6) 2ND REQUEST. PLEASE REVIEW 2010 FBC-B 404.6 |
| | ENCLOSURES OF ATRIUMS REQUIRE A 1 HOUR FIRE BARRIER |
| | CONSTRUCTION. |
| | COMMENT FROM 1ST REVIEW. EGRESS DOOR LABELED (I) IS |
| | INDICATED AS A "B" LABEL DOOR IN SCHEDULE, PLEASE REFER |
| | TO 2010 FBC-B TABLE 715.4 FIRE BARRIERS OF 1 HR REQUIRE |
| | A 45 MINUTE RATED FIRE DOOR, NOT A 20 MINUTE DOOR. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |