Plan Review Notes
Plan Review Notes For Permit 14090929
Permit Number 14090929
Review Stop B
Sequence Number 1
Notes
Date Text
2014-10-01 12:18:23BUILDING PLAN REVIEW
 PERMIT: 14090929
 ADD: 222 LAKEVIEW AVE. SUITE # 120
 CONT: GREEN CORPORATION
 TEL: (305)670-1000
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: WED. OCT. 01/2014
 ACTION: DENIED
  
 1) SHEET A-04 INDICATES THE (2) ELEVATORS AND MACHINE
 ROOM AS EXISTING, PLEASE CORRECT PLANS. THEY ARE UNDER
 REVIEW PERMIT # 14081026.
 THIS IS A HIGHRISE BUILDING, THE 2010 FBC-B 708.14.1
 REQUIRES ELEVATOR LOBBIES EVEN IF THIS PORTION OF THE
 BUILDING IS ONLY 5 STORIES TALL OR MEET ONE OF THE
 SEVEN EXCEPTIONS, THIS IS CONSIDERED NEW WORK. 2010
 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING. THE M3 SHEET
 DOES SHOW SF-1 FAN PRESSURIZING THE ELEVATOR SHAFTWAY.
 THE SHEET M2 NOTE2 ONCE THE SMOKE ALARM CLOSES VANT #
 1, THE VENTS LABELED # 2 WILL OPEN ON ACTUATION OF
 SMOKE ALARM OTHERWISE THEY ARE SET AND OPERATE AS A
 BAROMETER PRESSURE SENSOR.
  
 2) THE HOISTWAY WALLS AND ELEVATOR MACHINE ROOM WILL
 REQUIRE 2 HOUR FIRE RATED WALLS, UNDER THE SHAFTWAY
 PERMIT, THE ELEVATOR MACHINE ROOM DOOR IDENTIFIED AS
 DOOR (H) WILL NEED TO HAVE 1 1/2 HOUR OPENING
 PROTECTIVE. 2010 FBC-B 3006.4 MACHINE ROOMS AND
 MACHINERY SPACES &
 TABLE 715.4 OPENING PROTECTIVE TABLE 715.4.
  
 3) A LETTER FROM THE QUALIFIER OF BOTH THE ELEVATOR
 SHAFT CONTRACTOR (FASTRACK CORPORATION) AND TENANT
 BUILD-OUT CONTRACTOR MUST BE PROVIDED 7) BEFORE TENANT
 BUILD-OUT PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE ELEVATOR
 SHAFT HAS RECEIVED A CERTIFICATE OF COMPLETION,
 AGREEING THEY WILL WORK TOGETHER TO ACHIEVE CODE
 COMPLIANCE. THESE DOCUMENTS WILL NEED TO BE SIGNED BY
 THE QUALIFIER . PLEASE PROVIDE THE PERMIT NUMBER,
 ADDRESS WITH SUITE NUMBER WITHIN THE DOCUMENT.
  
 4) THE MAIN DOUBLE ENTRY DOORS TO THIS TENANT SPACE ARE
 WITHIN AN ATRIUM AND WILL NEED TO BE 1 HOUR FIRE RATED
 DOORS. 2010 FBC-B 404.6 ENCLOSURE OF ATRIUMS. ATRIUM
 SPACES SHALL BE SEPARATED FROM ADJACENT SPACES BY A
 1-HOUR FIRE BARRIER CONSTRUCTED IN ACCORDANCE WITH
 SECTION 707 OR A HORIZONTAL ASSEMBLY CONSTRUCTED IN
 ACCORDANCE WITH SECTION 712, OR BOTH. PLEASE SEE
 EXCEPTION # 3 FOR AN ACTIVE SMOKE CONTROL SYSTEM FOR
 THE ATRIUM.
  
 5A) THE A-04 SHEET DOES NOT DECLARE: 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY THE
 BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM
 CRITERIA AND DOCUMENTS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLE 503).
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
  
 5B) CLOSET # 105 DOOR (D) IS A 3'-0" WIDE DOOR AND
 LOCATED IN A CORRIDOR 5'-0" WIDE, PLEASE SEE 2010 FBC-B
 1008.1.9.11 DURING ITS SWING, ANY DOOR IN A MEANS OF
 EGRESS SHALL LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF
 THE REQUIRED WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY,
 OR LANDING, NOR PROJECT MORE THAN 7 INCHES (178 MM)
 INTO THE REQUIRED WIDTH OF AN AISLE, CORRIDOR,
 PASSAGEWAY OR LANDING, WHEN FULLY OPEN. DOORS SHALL NOT
 OPEN IMMEDIATELY ONTO A STAIR WITHOUT A LANDING.
 36"+18"(<50 OCC)= 4'-6"
 44"+22"(>50 OCC)= 5'-6"
  
 6) EGRESS DOOR LABELED (I) IS INDICATED AS A "B" LABEL
 DOOR IN SCHEDULE, PLEASE REFER TO 2010 FBC-B TABLE
 715.4 IN HOURS AND MINUTES & 715.4.3.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  