| Plan Review Notes For Permit 14090911 |
| Permit Number |
14090911 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-25 14:08:37 | B13 | | | | | | | | 2014-09-25 13:31:21 | 9/25/2014. PLEASE ADDRESS COMMENTS: | | | 1. REVISE FOLLOWING ITEMS: LOAD CALCULATION, PANEL | | | SCHEDULE DOES NOT ADDRESS ALL LOADS. | | | 2. PANEL SCHEDULE OVERCURRENT PROTECTIVE DEVICES PASTRY | | | WARMER,LARGE FREEZER (PANEL SCHEDULE SHOWS 15 KW LOAD | | | WITH 20 AMPERE OCPD, PASTRY WARMER NO LOAD WITH 2#8 ON | | | 20 AMPERE OCPD. | | | 3.SERVICE RISER DIAGRAM SHOWS 3#1/0 AWG WITH 200 AMPERE | | | OCPD. | | | 4. FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING | | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE | | | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
|